Permit Number: TC-COM-0726-01126
Parcel: 12106220A

Address:
5549 E LEE ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0726-01126
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2026 Commercial Mechanical Standard NOT REQUIRED
08/12/2026 Commercial Plumbing Standard NOT REQUIRED
08/13/2026 Fire New Construction Standard NOT REQUIRED
08/06/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting or electrical.
07/24/2026 Site Engineering Standard NOT REQUIRED
08/12/2026 Site Zoning Standard NOT REQUIRED
08/12/2026 Water - PDSD Standard NOT REQUIRED
08/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/13/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please indicate the type of roofing system that is proposed to be removed and identify the building numbers on the site plan. IBC 107.2.1
2. Structural Evaluation – Roof Replacement: Please provide documentation prepared by an Arizona Licensed design professional, identifying the existing and proposed roof assemblies and their respective dead loads (psf). The structural evaluation shall consider the complete roof assembly, including membrane, built-up roofing plies, asphalt, aggregate, insulation, cover boards and other permanent roofing components.
If this is an existing BUR assembly and the weight cannot be verified, identify the assumptions used to establish the existing roof dead load. As a preliminary screening value, 5 psf may be used to represent a typical gravel-surfaced BUR assembly, subject to verification by the design professional.
Please demonstrate that the proposed roof replacement does not adversely affect the existing structural system. Where the proposed assembly is lighter than the existing assembly, provide the calculated change in dead load and identify any other applicable structural considerations, including wind uplift, roof drainage/ponding, existing structural deterioration and changes to the roof attachment/load path.
Reference: 2024 IEBC applicable structural alteration provisions and 2024 IBC Chapter 16 requirements for structural loads, including roof dead loads.
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/06/2026 Commercial Electrical Standard REQUIRES RESUBMIT No modifications to the outdoor lighting or electrical.
07/23/2026 PDSD Application Completeness Express REVIEW COMPLETED