Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0726-01123
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/26/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/26/2026 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0726-01123 ADDRESS/PARCEL: 2465 N CAMPBELL AV TUCSON, AZ 85719 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. It appears the design outside air CFM for the 10 Ton West Unit should be 1,055 CFM instead of 880 CFM, based on the Mechanical New Work Plan. The Mechanical Demolition Plan and the air balance report show 880 CFM. Please provide a letter from the Engineer confirming the required outside air CFM. 2. Please also correct the actual outside air CFM entry for the 10-ton East Unit. |
||
| 10/26/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |