Permit Number: TC-COM-0726-01113
Parcel: 12112404E

Review Status: Requires Resubmit

Review Details: HAST - COMMERCIAL NEW ADD/ALT FAST TRACK v.2

Permit Number - TC-COM-0726-01113
Review Name: HAST - COMMERCIAL NEW ADD/ALT FAST TRACK v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2026 Commercial Building APPROVED
11/20/2026 Commercial Mechanical APPROVED
11/12/2026 Outdoor Lighting APPROVED
11/13/2026 Site Engineering APPROVED
11/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/17/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0626-00972 (1635 N CRAYCROFT RD TUCSON, AZ 85712)
TC-COM-0726-01109
TC-COM-0726-01110
TC-COM-0726-01111
TC-COM-0726-01112
TC-COM-0726-01113
TC-COM-0726-01114
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Reference sheet EP402, Duplex 1 power plan. Plans show the bathroom circuit 1B-13 in the bathroom receptacle AND at the Smoke Alarms for BOTH units. Circuit 1B-13 cannot be used outside the bathroom, and cannot cross into the other unit.
a. Bathroom requires dedicated circuit and cannot be used on the smoke detectors.
b. Provide a separate circuit for the smoke alarms.
2. Reference Sheet EP402, Duplex 1, Dryer circuit in the outdoor closet. Circuit 1B-26/28 is shown in both units. Update and correct.
3. Reference Sheet EP402: Provide GFCI protection for all kitchen receptacles, including the Range and receptacle shown above the range. NEC 210.8(A)(6) & 210.8(D)(8).
4. Reference Sheet EP402: Provide GFCI protection for the Dryer receptacle outlet per NEC 210.8(D)(11).
11/19/2026 Fire New Construction REVIEW COMPLETED