| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/07/2026 | Commercial Mechanical Standard | NOT REQUIRED | |||
| 08/07/2026 | Commercial Plumbing Standard | NOT REQUIRED | |||
| 08/10/2026 | Fire New Construction Standard | NOT REQUIRED | |||
| 08/07/2026 | Water - PDSD Standard | NOT REQUIRED | |||
| 08/10/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/06/2026 | Commercial Building Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0726-01097 ADDRESS/PARCEL: (815 W AUTO MALL DR TUCSON, AZ 85705) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976. COMMENTS: 1. Please submit a Site Plan. Locate the proposed shade structure. Draw the existing structure and label it, "To be Demolished". Show the distance in feet from the structure to the property line(s). 2. Please resubmit. |
||
| 08/03/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical/Outdoor Lighting Reviews TC-COM-0726-01097 (815 W AUTO MALL DR TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Note or show any electrical to the building. 2. Note or show any lighting fixtures attached to the building or inside. 3. Complete electrical plans will be required if electrical is going to the building. 4. Any outdoor lighting fixtures will be required to meet the requirements of the outdoor lighting code. Additional comments may be forthcoming. |
||
| 08/03/2026 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Commercial Electrical/Outdoor Lighting Reviews TC-COM-0726-01097 (815 W AUTO MALL DR TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Note or show any electrical to the building. 2. Note or show any lighting fixtures attached to the building or inside. 3. Complete electrical plans will be required if electrical is going to the building. 4. Any outdoor lighting fixtures will be required to meet the requirements of the outdoor lighting code. Additional comments may be forthcoming. |
||
| 07/24/2026 | Site Engineering Standard | REQUIRES RESUBMIT | Permit Activity Number: TC-COM-0726-01097 (1st Review) Project: REMOVE EXISTING SUNSHADE STRUCTURE AND INSTALL NEW 3 SIDED DETAIL BAY/ STRUCTURE. NO ELECTRICAL, PLUMBING OR MECHANICAL. Location: 815 W AUTO MALL DR Review Date: 7/24/2026 Reviewer: Marco Contreras – Engineering Associate - Site Engineering Reviewer Contact: Marco.contreras@tucsonaz.gov Related cases: Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering. To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Please do not mark or highlight changes in the drawings at this stage — revision markups are only used after a permit has been issued. Submit your response letter and updated plan set as two separate files. Site Engineering Review Comments: 1. The proposed detail bay/structure, and all other exterior modifications proposed at this commercial site will require the submission of a Development Package (Site plan) in accordance with UDC §7.4.3.E. Per UDC §3.3.3.G.2.c, A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. Please coordinate through email to confirm any additional studies required based on site conditions & reviewer comments. Note that the Development Package is a separate permit submittal, and must be processed independently of the building plans. 2. Site Engineering is unable to fully review and approve permit TC-COM-0726-01097 until the associated Development Package is reviewed and approved by all reviewers. |
||
| 08/06/2026 | Site Zoning Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Bobby Parsons Zoning Section Review PROJECT: TC-COM-0726-01097 815 W. Auto Mall Dr. Tucson, AZ 85705 New Detail Bay Structure (1st Review) TRANSMITTAL DATE: 8/6/2026 This site is located in the C-3 zone (UDC 4.7.22). Vehicle Rental & Sales is an allowed use in this zone subject to Use Specific Standards 4.9.9.G.1 & .2 (UDC Table 4-8-4). Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed. 1. Comment: As site work is being proposed (IE: new 3 sided detail bay/structure), a Development Package will be required. Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers. 2. Comment: Please include a detailed site plan with your next submittal showing where the proposed structure will be located. 3. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted. If you have any questions about this transmittal, please contact Zone1.Desk@tucsonaz.gov. |
||
| 07/21/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |