Permit Number: TC-COM-0726-01096
Parcel: 13811082A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0726-01096
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/16/2026 Commercial Mechanical Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01096
ADDRESS/PARCEL: 6350 S NOGALES HY TUCSON, AZ 85706

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Replacement of commercial AC units constitutes new work. Therefore, the submittal will require a heating/cooling load calculation for the building to justify the capacity of the unit being installed (Sections C403.3.1 and C403.2.2, IECC 2024). Alternatively, documentation showing the cooling capacity of the existing unit may be provided to demonstrate that the replacement unit is appropriately sized for the existing building load. The replacement unit shall also comply with Sections C403.3.2, C403.4, and C403.5, IECC 2024, for equipment performance, controls, and economizers.

While ventilation calculations are not required for this replacement, a test and balance report is required to verify that the total supply airflow and outdoor airflow are at least equal to that provided by the previous AC unit. Reference: Section C503.3, IECC 2024.

2. Also, please provide the weight of the existing HVAC unit to demonstrate that the existing supporting structure is adequate for the replacement equipment. Reference: Section 107.2.1 & 1604, IBC 2024.
07/14/2026 PDSD Application Completeness Express REVIEW COMPLETED