Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2026 Commercial Electrical Standard APPROVED Approved with comments added to plans:
Wire Tag #4: 2/0 ECG per NEC 250.122(F)(1)(b) & Table 250.122.
Wire Tag #5: 250 kcmil ECG per NEC 250.122(F)(1)(b) & Table 250.122.