Permit Number: TC-COM-0726-01062
Parcel: 13602001S

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0726-01062
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
N/A Addressing Validation PENDING ASSIGNMENT
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Commercial Mechanical Standard PENDING ASSIGNMENT
N/A Commercial Plumbing Standard PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
N/A Water - PDSD Standard PENDING ASSIGNMENT
07/24/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01062 (1333 S PANTANO PW TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Update the EEOR’s Seal to show signed date to match the currently adopted code, 2023 NEC, and to be dated after the ‘Owner Requested Changes’.
2. Maximum, 3 conductors in conduit for #8 cu in a 1/2 EMT.
Panel C, Circuit 6.
Panel B, Circuit 1.
Panel A1, Circuit 10.
3. Show clear working CU Units and for the new electrical panels, per NEC 110.26. Per the provided scale, the CU units are within the clear working space of the new panels, A1 and A2.
4. Show each structure supplied by only one branch circuit of feeder, NEC 225.30. Building A is shown with 2 feeders.
5. NEC 225.37 Identification.

Where a building or structure has any combination of feeders, branch circuits, or services passing through it or supplying it, a permanent plaque or directory shall be installed at each feeder and branch-circuit disconnect location denoting all other services, feeders, or branch circuits supplying that building or structure or passing through that building or structure and the area served by each.
6. You will need 3 new commercial new building permits for Building A, B, and C. When applying for the new permits, indicate which building the permit is for and add this comment in the description; "MASTER SET LOCATED AT TC-COM-0726-01062, WITH REVIEWS PERFORMED FOR (add new permit numbers and associated building numbers)"
7. You will need three separate addresses for each building. You will need to contact Pima County Addressing to get an address each building. Please contact Pima County Addressing to resolve issue. Addressing@pima.gov or 520-724-9512.
07/24/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0726-01062 (1333 S PANTANO PW TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Update the EEOR’s Seal to show signed date to match the currently adopted code, 2023 NEC, and to be dated after the ‘Owner Requested Changes’.
2. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code.
3. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan, both new and existing. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
4. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
5. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
6. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
7. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
8. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.
9. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

10. Specify any exceptions used.

11. Provide Curfew lighting controls If applicable Per section 403.
07/17/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-0726-01062 (1st Review)
Project: 3 New Building: Building A: Climate controlled Self Storage (19,896 SF) Building B: Self Storage (2,500 SF) Building C: Self Storage (3,400 SF)
Location: 1333 S PANTANO PW
Review Date: 7/17/2026
Reviewer: Marco Contreras – Engineering Associate - Site Engineering
Reviewer Contact: Marco.contreras@tucsonaz.gov
Related cases: TD-DEV-0626-00168

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering.
To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Please do not mark or highlight changes in the drawings at this stage — revision markups are only used after a permit has been issued. Submit your response letter and updated plan set as two separate files.
Site Engineering Review Comments:
1. Site Engineering has completed its review of the submitted building plan set and cross-referenced it against the associated Development Package. However, final approval of Commercial TC-COM-0726-01062 cannot be granted until the associated submission of the Development Package TD-DEV-0626-00168 has received full approval and has been issued. Per UDC §3.3.3.G, building permits for sites requiring a Development Package may not be issued prior to DP approval, as the building plans must be consistent with an approved site plan. Please resubmit for final approval once the Development Package has been approved and issued by all applicable reviewers.
07/15/2026 PDSD Application Completeness Express REVIEW COMPLETED If you have any questions about this review contact CDRC@tucsonaz.gov
This permit can be used for work being done to the existing building, it will also serve as a Master Permits for this shared plan set.
You will need 3 new commercial new building permits for Building A, B, and C. When applying for the new permits, indicate which building the permit is for and add this comment in the description; "MASTER SET LOCATED AT TC-COM-0726-01062, WITH REVIEWS PERFORMED FOR (add new permit numbers and associated building numbers)"