Permit Number: TC-COM-0726-01056
Parcel: 137070330

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0726-01056
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2026 Site Zoning Standard APPROVED
08/03/2026 Commercial Mechanical Standard NOT REQUIRED
08/03/2026 Commercial Plumbing Standard NOT REQUIRED
07/23/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
07/17/2026 Site Engineering Standard NOT REQUIRED
08/03/2026 Water - PDSD Standard NOT REQUIRED
08/03/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/13/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding this review, please contact CDRC@tucsonaz.gov.

ATTENTION: Parcel/addressing issue. The construction plan shows multiple units but the permit application does not have units attached and each building number will need its own permit for an addition alteration permit. I update this one to be for Unit A, but you will need to apply for a separate permit for Unit, B, C and D and there is a separate code case for each of these.
07/31/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Each unit will require a separate permit and this can be done by way of our master permit process where this first permit is the master permit. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/submitting-for-multiple-permits-on-one-plan-set.pdf
2. Please review the stated project valuation of $50,000.00. Based on the adopted fee schedule, the project square footage, and classification as a Level 3 (alteration area more than 50% of the building), the value derived from the default calculation is much higher than what was specified on the permit application.
3. Please provide a copy of the construction contract or detailed estimates to verify the project valuation. If additional information is not provided, the permit fees will be assessed based on the calculated valuation in accordance with IBC 109.3 and the adopted fee schedule
4. Provide the sealed fire damage assessment prepared for this property with the next submittal. IBC 107.2.1
5. Complete Architectural Plans Required
Provide complete architectural plans with sufficient graphic representation of the proposed work. Revise the plans to include the following information:
a. Provide a cover sheet or code data sheet containing the project information. 2024 IBC Section 107.2.1
b. List the edition year and title of all adopted codes applicable to this project, as adopted by the jurisdiction. 2024 IBC Section 107.2.1
c. Provide a drawing index listing all sheets included within the scope of this permit. 2024 IBC Section 107.2.1
d. Provide a detailed description of the proposed work included in the scope of this permit. For projects containing multiple tenant spaces or units, identify the work associated with each unit. 2024 IBC Section 105.3
e. Identify all deferred submittals on the plans and include a note stating that deferred submittal items shall not be fabricated or installed until reviewed and approved by the Building Official. Examples include prefabricated wood truss designs, delegated structural engineering, and other deferred items. 2024 IBC Section 107.3.4.1
f. Identify all exterior wall covering materials and provide references to the applicable installation details. For example, identify the exterior stucco assembly at the front wall where the proposed signage is to be installed. 2024 IBC Section 1404.1
g. Identify the specific exterior wall water-resistive barrier (WRB) to be installed behind each exterior wall covering. For example, identify the WRB for the stucco assembly at the front wall where the proposed signage is to be installed. 2024 IBC Section 1403.2
h. Provide construction details showing the installation of the water-resistive barrier, flashing, and weather protection at all exterior wall assemblies, including penetrations, transitions, and interfaces. For example, provide wall section details for the stucco assembly at the front wall where the proposed signage is to be installed. 2024 IBC Sections 107.2.4, 1402.2, and 1404.4
i. Provide building sections, drawn to scale, for each building and structure. Sections shall clearly identify floor, wall, roof, foundation, and structural assemblies. 2024 IBC Section 107.2.1
j. Clearly identify and detail all structural and architectural connections shown on the plans. 2024 IBC Section 107.2.1
k. Dimension ceiling heights and identify any projections or protruding objects affecting the required minimum headroom of 7 feet 6 inches. 2024 IBC Sections 1003.2 and 1207.2
l. Specifically identify all interior wall and ceiling finish materials. 2024 IBC Section 801.1
m. Provide complete building thermal envelope information, including insulation values, fenestration performance, and assembly details. The information shall be consistent with the submitted energy compliance documentation. 2024 IECC Sections C402.1 and C407.4

n. Provide complete roofing plans indicating roof sheathing type and thickness, fastening requirements, roof covering type, underlayment, flashing, edge metal, gutters, downspouts, roof drainage, and roof slope, as applicable. 2024 IBC Sections 107.2.1, 107.2.4, 1502, 1503, 1504, and the applicable roof covering provisions of Chapter 15.6. 6.
6. Demolition Plan Required
Provide a complete demolition plan that clearly identifies the extent of demolition and all existing construction to remain. The demolition plan shall include, at a minimum, the following:
a. Clearly identify all walls, doors, windows, ceilings, floors, roof components, structural elements, equipment, fixtures, and utilities to be demolished.
b. Clearly identify all existing construction, structural elements, equipment, and utilities that are to remain and be protected during construction.
c. Provide demolition keynotes, symbols, and/or shading that clearly distinguish between items to be removed, relocated, and remaining in place.
e. Where structural elements are removed or altered, provide supporting structural details and calculations prepared by the registered design professional demonstrating that the remaining structure complies with the applicable code requirements. For example, The roof plan and the demo plan show different areas of work
f. Revise the proposed construction plans to clearly correlate with the demolition plans so that the scope of demolition and new construction is consistent throughout the plan set. For example, The roof plan and the demo plan show different areas of work
2024 IBC Sections 107.2.1 and 107.2.4

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/23/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01056 (5101 S 12TH AV Unit:UNIT A TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide an electrical plan showing any/all electrical work. Plans shall include but may not be limited to items below and as necessary for the actual scope of work: >>> This cannot be deferred. Electrical to the new building shall be shown on the building plans.
3. Electrical demo plans.
4. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40. >>>
5. Provide a line diagram showing the new equipment being added or modified, NEC 110.2, 2018 IBC 107.1.
6. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
7. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
8. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
9. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24.
10. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10.
08/03/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
07/13/2026 PDSD Application Completeness Express REVIEW COMPLETED