Permit Number: TC-COM-0726-01053
Parcel: 106123500

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0726-01053
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/13/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01053 (3544 N ROMERO RD Unit:UNIT 190 TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Clarify if this is a new meter that is in addition to existing electoral meters, or is this the repair/replacement of an existing meter that is faulty? The repair of the existing service equipment requires the submission of a basic riser-diagram.
2. Provide an electrical riser diagram, NEC 230.9.
a. Show each meter and address/unit associated with each meter.
b. Show bus bar or equipment rating and AIC ratings of the new equipment.
c. Highlight the parts, conductors, equipment, etc, being repaired. Provide sizing and other info as needed to verify code compliance.

The addition of an additional meter will require additional information.
Demonstrate compliance with NEC 230.2 (Number of Services). May require written consent from the Building Official through appeal.
07/09/2026 PDSD Application Completeness Express REVIEW COMPLETED