Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0726-01047
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2026 | Site Zoning Standard | APPROVED | |||
| 07/30/2026 | Water - PDSD Standard | APPROVED | |||
| 07/22/2026 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 07/10/2026 | Site Engineering Standard | NOT REQUIRED | |||
| 08/03/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/09/2026 | Addressing Validation | REQUIRES RESUBMIT | If you have questions regarding this review, please contact CDRC@tucsonaz.gov. The address on the permit location 1220 S 6TH AV does not match the address on the uploaded documents (29 W . 22nd Street). Please either correct the address on the uploaded documents and resubmit or submit a change of address request in the permit sub-records. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and add the unit if needed. For help navigating sub records: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf |
||
| 07/30/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov 1. Please revise the construction documents and resubmit a complete plan set bearing the current original seal, signature, and date of each licensed design professional responsible for the preparation of the documents. Plans shall comply with the requirements of the Arizona Board of Technical Registration (AZBTR) and the 2024 International Building Code. Documents submitted with expired, missing, or otherwise invalid professional seals cannot be accepted for permit review. Code References: 2024 IBC Section 107.2.1 – Information on construction documents. Arizona Board of Technical Registration (AZBTR) – Requirements for sealed, signed, and dated professional documents. 2. Please revise the construction documents to reference the currently adopted City of Tucson amended codes. The code analysis and all applicable code references throughout the plans shall be updated to reflect the currently adopted codes listed below. Construction documents shall contain accurate and complete information in accordance with the adopted codes. Applicable codes include: 2024 International Building Code (IBC) 2024 International Existing Building Code (IEBC), where applicable 2017 ICC A117.1 Accessible and Usable Buildings and Facilities (referenced standard) 2024 International Mechanical Code (IMC) 2024 International Plumbing Code (IPC) 2023 National Electrical Code (NEC) 2024 International Fire Code (IFC) 2024 International Fuel Gas Code (IFGC) 2018 International Energy Conservation Code (IECC) City of Tucson/Pima County Outdoor Lighting Code City of Tucson Local Amendments to the adopted codes The current adopted codes and local amendments are available on the City of Tucson Planning and Development Services Department website. Code Reference: 2024 IBC Section 107.2.1 – Construction documents shall contain information of sufficient clarity to indicate the location, nature, and extent of the work proposed and demonstrate compliance with the applicable adopted codes and ordinances. 3. Please provide the complete structural calculations used in the design of this project. Calculations shall be prepared, signed, and sealed by the registered design professional responsible for the structural design and shall demonstrate compliance with the applicable provisions of the 2024 International Building Code. The calculations shall support all structural elements, connections, and load paths associated with the proposed work, including any new or modified structural components. Code References: 2024 IBC Section 107.2.1 – Construction documents shall contain sufficient information to demonstrate compliance with the applicable code. 2024 IBC Section 1603 – Construction documents shall include the required structural design information. 2024 IBC Chapter 16 – Structural design requirements. 4. Please provide a detailed scope of work for this project. The construction documents shall clearly describe the proposed work, including all new construction, alterations, repairs, additions, demolition, equipment installations, changes to building systems, and any modifications to the existing building or site. The scope shall be consistent throughout the plans and sufficiently detailed to allow the proposed work to be reviewed for compliance with the applicable codes. Code Reference: 2024 IBC Section 107.2.1 – Construction documents shall be of sufficient clarity to indicate the location, nature, and extent of the work proposed and demonstrate compliance with the provisions of the code and applicable laws, ordinances, rules, and regulations. 5. Please provide the most recent Certificate of Occupancy (C of O) for the tenant space. The Certificate of Occupancy is required to verify the existing occupancy classification, approved use, occupant load (if applicable), and any conditions or limitations associated with the space. This information is necessary to determine compliance of the proposed work with the applicable provisions of the 2024 International Building Code. Code References: 2024 IBC Section 107.2.1 – Construction documents shall contain sufficient information to demonstrate compliance with the applicable provisions of the code. 2024 IBC Section 111 – Certificate of Occupancy. Please contact me if you have any questions about the above comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 07/22/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0726-01047 (1220 S 6TH AV TUCSON, AZ 85713) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. There is a callout for a Kitchen equipment E13, but the Kitchen Equipment Feeder Schedule does not have an E13. Please correct. 2. Panel Schedule 'K2', circuits 5 & 7, show Kitchen equipment E12a and E12b, but the Kitchen Equipment Feeder Schedule has the DBL CONV OVEN as E13a and E13b. Please correct. 3. GFCI Protected per NEC 210.8(D)(8), (9), (10). Double Convection Ovens, E13a, E13b. Readily accessible per NEC 210.8. 4. GFCI Protected per NEC 210.8(D)(7). Dish Machines, E37A and E37B. Readily accessible per NEC 210.8. 5. The following Kitchen Equipment items could not be found on the Power Plan, E11, E14a, E14b, E56. Please indicate the location of these items and their electrical connection points. Receptacle, disconnect? 6. Note or show all conduits passing into or out-of the walk-in freezer/cooler units, with sealant and expansion joints per NEC 300.7(A) & (B). Provide detail as necessary. |
||
| 07/30/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0726-01047 ADDRESS/PARCEL: 1220 S 6TH AV TUCSON, AZ 85713 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Please provide heating and cooling load calculations to justify the heating/cooling capacity of the HVAC Equipment. Reference: Section C403.1.1 and C502.3.3, IECC 2024. 2. COMcheck submitted indicates compliance with the 2012 IECC. Please provide an updated COMcheck Certificate demonstrating compliance with the applicable 2024 IECC requirements. 3. Please show the size, routing, and termination of the condensate drains from the new HVAC units. Reference: Section 307.2.1, IMC 2024 as amended by the City of Tucson. |
||
| 07/30/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0726-01047 ADDRESS/PARCEL: 1220 S 6TH AV TUCSON, AZ 85713 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Provide sizing calculations for the grease interceptor. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson. 2. All code references throughout the plan set shall identify the applicable adopted codes, including the 2024 I-Codes (IBC, IMC, IPC, IECC etc.) as adopted and amended by the City of Tucson. Reference: Section 107.2.1, IBC 2024. 3. For the new grease interceptor, please submit proper documentation for the Pima County Industrial Wastewater Review. a. Contact Kelsey.McMonagle@pima.gov or Adam.DeLaTorre@pima.gov for review and assessment of the proposed grease interceptor b. Please submit the email from IWC indicating the approval of your interceptor to satisfy this condition. |
||
| 08/03/2026 | Fire New Construction Standard | REQUIRES RESUBMIT | Resolve all building comments. john.vincent@tucsonaz.gov 5203495581 |
||
| 07/09/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |