Permit Number: TC-COM-0726-01040
Parcel: 12307294C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0726-01040
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2026 Commercial Electrical Standard APPROVED
07/29/2026 Site Zoning Standard APPROVED
07/28/2026 Water - PDSD Standard APPROVED
07/22/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
07/10/2026 Site Engineering Standard NOT REQUIRED
07/30/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/30/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please revise the plans to include a structural detail demonstrating how the commercial kitchen hood is connected to, supported by, and laterally braced from the building structure. The detail shall clearly identify all attachment methods, support members, connection hardware, and required bracing necessary to provide a complete load path and ensure structural stability. 2024 IBC Section 107.2.1.
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/28/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of RTU-1 and RTU-2. Reference: Section C403.1.1 and C502.2.3, IECC 2024.
2. Show that the walk-in cooler and the walk-in freezer meet the efficiency requirements of Tables C403.12.2.1(2) and Table C403.12.2.1(3), IECC 2024. Reference: Section C403.12, IECC 2024.
3. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2024.
4. Footnote b on Table 403.3.1.1, IMC 2024 states that no air from the kitchen may be recirculated to any other space. RTU-1 appears to be serving both the kitchen and the non-kitchen areas. Reference: Section 403.2.1 (3), IMC 2024.
5. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2024.
6. Verify that the evaporative cooling section of the makeup air unit is equipped with a recirculating water system. Reference: Section 928.1, IMC 2024 and ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.gov/viewdocument/?docName=http://www.azleg.gov/ars/45/00313.htm).

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
07/28/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Southwest Gas, the local gas utility, provides natural gas at 7” WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7” WG or greater will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. Reference: Section 402.1, IFGC 2024.
2. Floor sinks in the kitchen shall discharge through a grease interceptor (e.g., see prep sink 5.13). Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson
3. Provide sizing calculations for the proposed grease interceptor. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson.
4. Provide a vent downstream of the gravity grease separator to protect the seal for the grease separator. Reference: Section 1003.9, IPC 2024, as amended by the City of Tucson.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
07/26/2026 Fire New Construction Standard REVIEW COMPLETED
07/08/2026 PDSD Application Completeness Express REVIEW COMPLETED