Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0726-01038
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/28/2026 | Commercial Plumbing Standard | APPROVED | |||
| 07/28/2026 | Water - PDSD Standard | APPROVED | |||
| 07/22/2026 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 07/10/2026 | Site Engineering Standard | NOT REQUIRED | |||
| 07/29/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/08/2026 | Addressing Validation | REQUIRES RESUBMIT | If you have questions regarding this review, please contact CDRC@tucsonaz.gov. ATTENTION: Parcel/addressing issue. The construction plan shows multiple units but the permit application does not have units and the construction plan does not show unit numbers. The location does not have units attached to the address in our system. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and add the unit numbers. After address/units have been added or verified you'll need to submit an address change request to update this record in the sub records tab. If multiple units are being worked on and not common space, then a permit may be required for each unit. For help navigating sub records: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf |
||
| 07/29/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov 1. Please identify the type A units on the plans and provide the information and technical drawings as required by IBC 1108.6.2.2.1 and 2017 ICC A117.1 Chapter 11. 2. Please review the stated project valuation of $25,000.00. Based on the adopted fee schedule, the project square footage, and classification as a Level 2 alteration area less than 50% of the building), the value derived from the default calculation is much higher than what was specified on the permit application. Please provide a copy of the construction contract or detailed estimates to verify the project valuation. If additional information is not provided, the permit fees will be assessed based on the calculated valuation in accordance with IBC 109.3 and the adopted fee schedule. Please contact me if you have any questions about the above comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 07/22/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0726-01038 (1502 E 10TH ST TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, NEC 210.11(C)(3) and NEC 210.52(D). Cannot share with the Master lighting circuit. 2. Provide GFCI protection for all kitchen receptacles, including the Range and Fridge, per NEC 210.8(A)(6) & 210.8(D)(8). Shall be readily accessible, per NEC 210.8, and may require GFCI breakers. 3. Provide GFCI protection for all receptacles within the laundry area, per NEC 210.8(A)(11) & 210.8(D)(11). Must include the dryer, and be readily accessible, per NEC 210.8. 4. Show locations of each smoke alarm, [NFPA 72]. Must be in the immediate vicinity; outside the bedrooms. Notate that all smoke alarms must be interconnected with a power source from the building wiring and be equipped with battery backup. 5. Kitchen peninsula is missing receptacle, or provisions for future receptacle installation: NEC 210.52(C)(2) Island and Peninsular Countertops and Work Surfaces. Receptacle outlets, if installed to serve an island or peninsular countertop or work surface, shall be installed in accordance with 210.52(C)(3). If a receptacle outlet is not provided to serve an island or peninsular countertop or work surface, provisions shall be provided at the island or peninsula for future addition of a receptacle outlet to serve the island or peninsular countertop or work surface. |
||
| 07/28/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0726-01038 ADDRESS/PARCEL: 1502 E 10TH ST TUCSON, AZ 85719 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Booster fans are prohibited. Domestic booster fans shall not be installed in dryer exhaust systems. The specified dryer booster fan is not listed to UL-705 DEDPV. Reference: Section 504.6, IMC 2024. |
||
| 07/29/2026 | Site Zoning Standard | REQUIRES RESUBMIT | FROM: Olga Salazar PDSD Zoning Review Section PROJECT: TC-COM-0726-01038 – Multifamily Tenant Improvement (1st Review) 1502 East 10th Street TRANSMITTAL DATE: July 29, 2026 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: On the cover sheet, the total building area is listed as 11,421 sq. ft. However, the combined building areas shown on the site plan for the existing 2-story building (5,710.5 sq. ft.) and accessory building (240 sq. ft.) total 5,950.5 sq. ft. Please correct this information to ensure consistency. If you have any questions about this transmittal, contact Olga Salazar at Olga.Salazar@tucsonaz.gov. |
||
| 07/26/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 07/08/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |