Permit Number: TC-COM-0726-01034
Parcel: 133225020

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0726-01034
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2026 Commercial Building Standard APPROVED
09/08/2026 Commercial Electrical Standard APPROVED
09/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/14/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Comment not resolved; the “concept services” documents were not found in the submittal. [Initial comment: Unless the proposed Type I kitchen hood has been factory-built and tested in accordance with UL 710, The construction of the hood shall comply with the requirements of Sections 507.1.4, 507.1.5, 507.1.6, 507.2.3, 507.2.5, 507.2.8, 507.2.9, 507.2.10, 507.2.11 and 507.3.1, IMC 2018. Reference: Section 507.1, IMC 2024.]
2. Comment not resolved; the “concept services” documents were not found in the submittal. [Initial comment: Show that the hood installation complies with Section 507.2.6, IMC 2024 with regard to a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall and extending 18” beyond the hood.]

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
09/14/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Comment not resolved; signage for the handwash sinks not found in the submittal. [Initial comment: A hand wash sink located in the kitchen area shall either discharge through a grease interceptor or have a sign posted above it stating: “HANDWASH SINK ONLY! NO FOOD PREPARATIONOR DISHWASHING ALLOWED”. Reference: Section 1003.3(A), IPC 2024 as amended by the City of Tucson.]
2. Comment not resolved; the downstream pressure settings were not found in the submittal. [Initial comment: Revise the natural gas pipe drawing on M102 to show the downstream pressure of any pressure reducing valves.]
09/14/2026 Fire New Construction Standard REVIEW COMPLETED
08/21/2026 PDSD Application Completeness Express REVIEW COMPLETED