Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0726-01018
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/20/2026 | Commercial Building | APPROVED | |||
| 07/17/2026 | Commercial Electrical | APPROVED | Approved with notes added to plans: GFCI per NEC 210.8(B)(14). Readily accessible per NEC 210.8. |
||
| 07/20/2026 | Commercial Plumbing | APPROVED | |||
| 07/20/2026 | Site Zoning | APPROVED | |||
| 07/20/2026 | Water - PDSD | APPROVED | |||
| 07/10/2026 | Site Engineering | NOT REQUIRED | |||
| 07/20/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/20/2026 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Revise the ventilation calculation for FC-2. The receptionist area is most similar in terms of occupant density and activities to a main entry lobby than to an office. Reference: Section 403.3.1, IMC 2024. 2. The proposed dryer booster fan is not listed to UL 705 DEDPV supplement and may not be used. Reference: Section 504.6, IMC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 07/17/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 07/06/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |