Permit Number - TC-COM-0726-01016
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2026 Site Engineering Standard NOT REQUIRED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Commercial Electrical Standard PENDING ASSIGNMENT
N/A Commercial Mechanical Standard PENDING ASSIGNMENT
N/A Commercial Plumbing Standard PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
N/A Water - PDSD Standard PENDING ASSIGNMENT
08/13/2026 Addressing Validation REQUIRES RESUBMIT If you have any questions, please contact cdrc@tucsonaz.gov

Please resubmit construction documents with full address, including building number and unit number on all pages after this initial review.

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
08/18/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01016 (5180 E 22ND ST Unit:BLDG D UNIT 89 TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide plans relevant to the scope of work being done. Plans from 2014 are not appropriate for this scope of work. Plans must show compliance to the currently adopted codes as listed above.
3. Provide Service Surge Protection per NEC 230.67(D). All downstream dwelling units require surge protection when replacing the service equipment.

Additional comments may be forthcoming when provided appropriate electrical plans for the given scope of work.
08/13/2026 PDSD Application Completeness Express REVIEW COMPLETED