Permit Number: TC-COM-0726-01011
Parcel: 13613001W

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0726-01011
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2026 Site Engineering Standard APPROVED
07/24/2026 Site Zoning Standard APPROVED
07/24/2026 Water - PDSD Standard APPROVED
07/27/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/27/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01011
ADDRESS/PARCEL: (9410 E GOLF LINKS RD TUCSON, AZ 85730)
TC-COM-0526-00787 (3002 E GRANT RD Unit:UNIT 2 TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. SHEET G0.1
a. Hood
i. Thank You for submitting the Structural Calculation file. I looked for the hood mounting structural calculation, however I could not find it within this document.
ii. Please provide structural calculation and detail drawings as to how the hood is mounted/hung from above.
b. CODE DATA
i. Occupancy Group
1. Shouldn’t this establishment be A2 per IBC 303.3. (NOTE: the C of O for the Taco Bell was A2)
2. The Code Data shows M.
3. Please make the necessary correction.
ii. Fire Sprinkler
1. I’ve marked this establishment within the Certificate of Occupancy as having no fire sprinkler.
2. Just for the record, please add an entry indicating whether there is fire sprinkler system.
c. OCCUPANT LOAD
i. Flex Seating
1. The floor plan shows 20 actual chairs.
2. The calculation list shows 24.
3. Please correct this.
d. EXIT ANALYSIS
i. Maximum Common Path of Egress Travel Distance per IBC Table 1006.2.1 is 75’.
ii. 30’ Maximum is shown on the sheet.
iii. Please make the necessary correction.
2. SHEET A1.1
a. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background. IBC 1010.1.9.4This permit is proposing to use the public restroom.
b. Please a note reflecting this on both the front door and the back door.
3. SHEET I1.2
a. Enlarged Restroom Plan
i. Turning space is shown as 60”.
ii. The turning space shall be a circular space with a 67-inch minimum diameter. ICC A117.1 sec 304.3.1.1
iii. Please make the necessary correction.
4. MENU BOARD CANOPY
a. Please obtain the structural calculation from the manufacturer.
b. Please provide detail drawings at the intersection of the canopy and the post.
c. Please provide detail drawings at the post base and the footing. Specify all the components to complete the information installation.
5. Please resubmit.
07/20/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0726-01011 (9410 E GOLF LINKS RD TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Update General Kitchen Equipment Note #1, on sheet E4.0, to include the following or similar: GFCI protection for all appliances per NEC 210.8(D).
May require GFCI breakers to maintain ready access per NEC 210.8.
07/24/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01011
ADDRESS/PARCEL: 9410 E GOLF LINKS RD TUCSON, AZ 85730

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Show that the walk-in cooler and walk-in freezer comply with the construction and efficiency requirements of Sections C403.12.2 and C403.12.2.1, IECC 2024.
2. The drawings show return air taken from the kitchen area by HP-1 being recirculated and supplied to the office and restrooms. In accordance with Footnote (b) of Table 403.3.1.1, air from commercial kitchen spaces shall not be recirculated to other occupancies or spaces. Please revise the design as necessary to demonstrate compliance and update the plans accordingly. Reference: Table 403.3.1.1, Footnote (b), IMC 2024.
3. Please revise the ventilation calculation table (Sheet M3.0). The storage, wash area, cooking, and drive-through areas shall be classified as kitchen (cooking) areas due to recirculated air from HP-1 originating from the kitchen space. Please verify that the correct square footage, occupant density, cfm/person, and cfm/ft² values are provided based on Table 403.3.1.1. Reference: Section 403.3.1.1, IMC 2024.
07/24/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01011
ADDRESS/PARCEL: 9410 E GOLF LINKS RD TUCSON, AZ 85730

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Hand sinks in the kitchen area are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” Please provide signage at both hand sink locations indicating that the sinks are to be used for handwashing only. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson.
2. Floor sinks in the kitchen areas shall discharge through a grease interceptor. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson.
3. Please verify that the distance from the hot water source to the hot water termination for the lavatories complies with the requirements of Section C404.5, IECC 2024
07/24/2026 Fire New Construction Standard REQUIRES RESUBMIT -Sheet G0.1, code data. Your occupancy classification is listed as a mixed occupancy M/B. It appears this is an A2 occupancy per IBC/IFC definitions.
-Sheet G0.1, Deferred submittals. You currently list Fire Alarm as a deferred submittal. Verify this building has a fire alarm that needs modification.
-If using bulk CO2 for beverage dispensing (system >100lbs CO2), a CO2 gas detection alarm will be required per IFC 5307.
john.vincent@tucsonaz.gov
5203495581
07/20/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0726-01011 (9410 E GOLF LINKS RD TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf


1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code.
2. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan, both new and existing. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
3. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
4. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
5. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
6. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
7. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.
8. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

9. Specify any exceptions used.

10. Provide Curfew lighting controls If applicable Per section 403.
07/02/2026 PDSD Application Completeness Express REVIEW COMPLETED