Permit Number: TC-COM-0726-01007
Parcel: 133231420

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0726-01007
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2026 Commercial Building APPROVED
07/16/2026 Commercial Electrical APPROVED
07/15/2026 Site Zoning APPROVED
07/17/2026 Water - PDSD APPROVED
07/10/2026 Site Engineering NOT REQUIRED
07/17/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/17/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01007
ADDRESS/PARCEL: 7725 E BROADWAY BL TUCSON, AZ 85710

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please provide ventilation calculations demonstrating compliance with the minimum outdoor air and exhaust ventilation requirements. Reference: Section 1008.1, IEBC 2024 & Table 403.3.1.1, IMC 2024.
07/17/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0726-01007
ADDRESS/PARCEL: 7725 E BROADWAY BL TUCSON, AZ 85710

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please verify that the distance from the hot water source to the hot water termination for the lavatory complies with the requirements of Section C404.5, IECC 2024 (e.g., 24” for ½” hot water supply piping).
2. Please specify a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds. Reference: Section 412.13, IPC 2024, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Provide a detail of the water heater installation above the mop sink, including the method of support, excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1 [connections & SOV], 504 [Safety devices], 606.1 [valves], 607.2 [recirculation], and 607.3 [thermal expansion control], IPC 2024.
07/17/2026 Fire New Construction REVIEW COMPLETED
07/02/2026 PDSD Application Completeness Express REVIEW COMPLETED