Permit Number: TC-COM-0725-01443
Parcel: 11811015Q

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0725-01443
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2025 Site Engineering APPROVED
08/15/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/15/2025 Commercial Building REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 8/13/2025 8:47:41 PM
1. General / Geotechnical Report: Please provide a copy of the site-specific geotechnical report for this project. The
report should support the appropriateness of the selected foundation system for the project site. All submitted
geotechnical reports must be dated no later than three years from the submittal date. Outdated reports must be
accompanied by a letter from a qualified geotechnical engineer stating that the report requirements are still valid, or
stating what items may have changed. All building code references must be updated to the current code adopted by
the City.


Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Approved with Comments
Reason:
Date Completed : 8/3/2025 3:34:50 PM
08/15/2025 Commercial Electrical REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 8/6/2025 10:47:56 AM
1. E401 ENLARGED ELECTRICAL POWER PLAN: Shall call out conductor sizes (to include ground size also) for all
circuits larger than 20 amps in panel AVI-2 or show this information on Detail 1.
2. E401 ENLARGED ELECTRICAL POWER PLAN: Should calculate the fault current for panel AVI-1 to show that KAIC
rating is sufficient. This is a required calculation for Tucson electrical permit submittals. However, this requirement is
waived for this review as the EOR selected 22 KAIC for the AVI-1 panel and the long length of the currently selected
feeder will reduce the fault current to a low value.
3. E402 ENLARGED ELECTRICAL LIGHTING PLAN: Key Note 1 is in wrong position/location and should be corrected.
08/15/2025 Commercial Mechanical REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 8/15/2025 11:04:21 AM
1. General - Provide the required ventilation as per 2018 IMC Section 403.3.1.1.
2. General - Provide what type of AVI equipment is to be housed in this structure. Specify what type of fuel equipment
uses. Is fuel going to be housed in this structure? - 2018 IECC Section C103.2Information on construction documents.
- 2018 IBC Section [A]107.2.1Information on construction documents.
3. General - Provide exhaust. - 2018 IMC Section 502.1 General
08/07/2025 Outdoor Lighting REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0725-01443 (775 W SILVERLAKE RD TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan. This structure appears to be on parcel 11811015L and not the addressed location on the plans.
2. List the Lighting Area per OLC chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
4. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).
5. Provide manufacture’s specification sheets for outdoor lighting fixtures.
6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

7. Specify any exceptions used.

8. Provide Curfew lighting controls If applicable Per section 403 and Table 601.3.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/12/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0725-01443 - TD-DEV-0725-00186
775 W SILVERLAKE RD - I-1
Transportation Service: Land Carrier - Vehicle inspection drive-through tunnel shelter (1st Review)

TRANSMITTAL DATE: ‎March 21, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the I-1 zone (UDC 4.7.29). Transportation Service: Land Carrier is an approved use in the zone (UDC Table 4.8-5), subject to Use Specific Standard 4.9.13.Q

1. As development plan (DP) TD-DEV-0725-00186 has not completed it’s 1st review Zoning will not review the building plans and will review on the next submittal.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/13/2025 Fire New Construction REVIEW COMPLETED
07/31/2025 PDSD Application Completeness Express REVIEW COMPLETED