Permit Number: TC-COM-0725-01439
Parcel: 11105046E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0725-01439
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2025 Commercial Electrical Standard APPROVED
08/25/2025 Site Zoning Standard APPROVED
08/20/2025 Water - PDSD Standard APPROVED
08/04/2025 Site Engineering Standard NOT REQUIRED
08/25/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/20/2025 Commercial Building Standard REQUIRES RESUBMIT 1. Cover Sheet Revise the area notes. There is no livable areas in these plans. Clearly list the following; Total Square Footage of the Building. Type of Construction. Occupant Load. Occupancy Type Sprinklered Building Fire Alarm Yes or No
2. Cover sheet List ICC A117 as accessibility code adopted by the City of Tucson.
3. Sheet A1.01 Show location of Accessible Parking and Path of Travel into the business. Per IBC Chapter 11.
4. Sheet A1.01 Show the accessibly entrance. IBC Chapter 11
5. Sheet A2.00 Provide a structural design for the new opening in the rated wall. Plans and calculations shall be sealed by an Arizona registrant.
6. Sheet A2.01 Provide structural plans and calculations for the new double door opening in the existing CMU Wall.
7. Sheet A2.01 Provide details for the new interior type 1 wall. Provide a structural plan and calculations.
8. Sheet A2.03 Show all required exit signs required in the IBC Chapter 10.
9. Sheet A11.01 The doors, hardware and frames need to be listed with manufactures information for plan review. The plan shows rated doors where the 3 hour wall was removed.
08/20/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Sheet M0.01 Provide outside air calculations showing required vs supplied.
2. Sheet M1.01 Clearly identify all new Mechanical Equipment and Duct work.
08/20/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Sheet A2.03 Are you making any modifications to the plumbing system?
08/18/2025 Fire New Construction Standard REQUIRES RESUBMIT -I do not understand your occupancy and exiting plan, sheet A2.03. You have the large room labeled as showroom but classified as storage (S2). S2 is storage for noncombustible materials. Please explain.
-Depending on the classification of the space, you cannot exit through a storage room if the room will be considered a showroom (M). Exiting will be reevaluated once the spaces are clearly defined. Please see IFC 1016.2 #6 for possible exception.
john.vincent@tucsonaz.gov
5203495581
08/13/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0725-01439 (3660 E FORT LOWELL RD TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf


1. The addition of the two new outdoor lighting fixtures requires compliance with the Outdoor Lighting Code, OLC 102.4.2.
2. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
3. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
4. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).
5. Provide manufacture’s specification sheets for outdoor lighting fixtures.

6. Specify any exceptions used.

7. Provide Curfew lighting controls If applicable Per section 403 and Table 601.3.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/20/2025 Water - PDSD Standard REQUIRES RESUBMIT Water Review to be done by City of Tucson
07/31/2025 PDSD Application Completeness Express REVIEW COMPLETED