Permit Number: TC-COM-0725-01421
Parcel: 11917020C

Address:
3520 S 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0725-01421
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2025 Commercial Plumbing Standard APPROVED
08/12/2025 Site Engineering Standard APPROVED
08/19/2025 Water - PDSD Standard APPROVED
08/19/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/19/2025 Commercial Building Standard REQUIRES RESUBMIT Sheet A1.0; For questions regarding Plan Review comments please contact: Dino M. Accardo, MCP, CBO, E: daccardo@willdan.com. Fire Plan Review, Civil Engineering and Planning/Zoning are NOT within the scope of this review. All applicable comments will be followed with the initials, DMA.

1. Sheet A1.0, 2018 IBC Ch 16; Provide structural calculations for structure. DMA
2. Sheet A.0, 2018 IBC Ch 17; Submit a completed Special Inspection Certificate. DMA
3. Sheet A1.0, 2018 IBC Ch 18; Provide a selaed soils report for site, DMA
4. Sheet A1.0, 2018 IBC Ch 3; Provide a code compliant occupancy classification. DMA
5. Sheet A2.0, 2018 IBC Table 602; Fire-resistance rating for exterior walls must be provided for structure. DMA
08/08/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0725-01421 (3520 S 6TH AV TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2018 International Energy Conservation Code (IECC).


1. Provide complete compliance with the 2018 IECC for the interior lighting, including sensors and lighting controls as required. (typically COMcheck).


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/19/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Sheet M1.0, 2018 IMC Sec 506, 507 and 508; Submit a complete kitchen hood design, equipment schedule with appliances, and associated details and calculations. DMA
08/14/2025 Fire New Construction Standard REQUIRES RESUBMIT Please review occupancy classification, IFC 203.3 (2024 ed.) Business Group B definition. I believe you meet the definition of a B and not an A2 unless the plan is to allow food and drink consumption.
john.vincent@tucsonaz.gov
5203495581 call/text
08/08/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0725-01421 (3520 S 6TH AV TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. This Outdoor Lighting Plan shall include all light sources for the entire parcel. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
2. List the Lighting Area per OLC chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
4. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).
5. Provide manufacture’s specification sheets for outdoor lighting fixtures.
6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

7. Specify any exceptions used.

8. Provide Curfew lighting controls If applicable Per section 403 and Table 601.3.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/13/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0725-01421 - TD-DEV-0424-00124
3520 S 6TH AV. - C-2
Food Service (1st Review)

TRANSMITTAL DATE: ‎August 13, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Food Service is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

1. The drawing index does not match the sheets that were submitted.

2. The development package sheets provided in the building plan set either need to be the stamped approved development package sheets, marked for reference only, or removed from the building set. If you elect to mark for reference only, do not mark the utility plans and if you elect to remove the plans leave the utility plans in the so Plumbing can review.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/28/2025 PDSD Application Completeness Express REVIEW COMPLETED