| 08/04/2025 | Commercial Electrical Express | APPROVED | |||
| 08/04/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/04/2025 | Commercial Mechanical Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0725-01412 ADDRESS/PARCEL: (125 S LINDA AV TUCSON, AZ 85745) The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. COMMENTS: 1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. 2. Please resubmit |
||
| 07/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |