Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-0725-01410
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/06/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Comment not addressed. [Second comment: The submitted cooling load calculations indicate that units with less cooling capacity will accommodate the cooling requirements. Provide justification for the units selected for RTU-1 and RTU-2.] [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.] 2. Comment not addressed. [Second comment: Data not included in submittal.] [Initial comment: Show that the walk-in cooler and the walk-in freezer meet the efficiency requirements of Section C403.10.2.1, IECC 2018.] |
||