Permit Number: TC-COM-0725-01410
Parcel: 134162140

Address:
7101 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0725-01410
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2025 Commercial Building Standard APPROVED
10/21/2025 Commercial Electrical Standard APPROVED
11/06/2025 Commercial Plumbing Standard APPROVED
11/07/2025 Site Zoning Standard APPROVED Approved with TD-DEV-0525-00137
11/06/2025 Water - PDSD Standard APPROVED
11/12/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/06/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. The submitted cooling load calculations indicate that units with less cooling capacity will accommodate the cooling requirements. Provide justification for the units selected for RTU-1 and RTU-2. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.]
2. The COMcheck requirements are based on the 2021 IECC, not the 2018 IECC. The cooling capacity of the proposed AC units is 130.0 MBH but the stated minimum efficiencies are for unit with cooling capacities over 135 MBH. Coordinate the code requirements, the unit capacities, and the actual unit efficiencies. [Initial comment: Show that the proposed HVAC equipment meets the minimum performance requirements of Section C403.3.2, IECC 2018.
3. Data not included in submittal. [Initial comment: Show that the walk-in cooler meets the construction requirements of Section C403.10.2, IECC 2018.]
11/04/2025 Fire New Construction Standard REVIEW COMPLETED
10/17/2025 PDSD Application Completeness Express REVIEW COMPLETED