Permit Number: TC-COM-0725-01410
Parcel: 134162140

Address:
7101 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0725-01410
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2025 Site Engineering Standard APPROVED
08/18/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/15/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Sheet G000: Please amend the plans to show Signage as a separate permit instead of a deferred submittal. IBC 107.2.1
2. Sheet G000: Please amend the plans to use the 2009 ICC A117.1 for the governing Accessibility Code
3. Please amend the plans to remove NFPA where they can be replaced with Code references from our adopted code. IBC107.2.1 Treat as a typical note. For example, Sheet A601 Door Hardware, Door notes #2
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/08/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0725-01410 (7101 E 22ND ST TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. Provide overcurrent protection for Panel B feeder per NEC 215.3 & 240.4. REF sheet E600, panel A, circuits 55,57,59.
2. Provide complete compliance with the 2018 IECC for the interior including sensors and lighting controls as required. (typically COMcheck).


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/18/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
2. Show that the proposed HVAC equipment meets the minimum performance requirements of Section C403.3.2, IECC 2018
3. Verify that the specified HVAC systems are provided with controls that are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. Reference: Section C403.4.2.3, IECC 2018.
4. Show that the walk-in cooler meets the construction requirements of Section C403.10.2, IECC 2018.
5. Show that the walk-in cooler and the walk-in freezer meet the efficiency requirements of Section C403.10.2.1, IECC 2018.
6. Condensate drains shall be terminated at an approved disposal location (i.e. not onto the roof deck as stated in detail 13/P700). Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.
7. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.
08/18/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Indirect waste receptors shall not be installed in concealed spaces. Provide ready access to the waste receptor shown in detail 18/P700. Reference: Section 802.4, IPC 2018.
2. Provide sizing calculations and specifications for the proposed grease interceptor. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
08/13/2025 Fire New Construction Standard REQUIRES RESUBMIT -Remove fire sprinklers and fire alarm from deferred submittals, sheet G000, if you're not installing these.
-TFD/COT has adopted the 2024 IFC. You currently list the 2018. Sheet G000.
-Sheet A601 (door notes). Remove reference to NFPA 101. COT/TFD does not adopt NFPA 101. You can reference IBC, IFC and ADA standards as it pertains to doors and hardware.
john.vincent@tucsonaz.gov
5203495581
08/12/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0725-01410 - TD-DEV-0525-00137
7101 E 22ND ST. - C-2
Food Service (1st Review)

TRANSMITTAL DATE: ‎August 12, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Food Service is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

1. Clarify why the building square footage, 2,385 is different than what is shown on the DP. Square footage should match.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/14/2025 Water - PDSD Standard REQUIRES RESUBMIT Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
08/08/2025 Outdoor Lighting Standard REVIEW COMPLETED Outdoor lighting per shell permit TC-COM-0625-01127 (7101 E 22ND ST TUCSON, AZ 85710)
07/25/2025 PDSD Application Completeness Express REVIEW COMPLETED