Permit Number: TC-COM-0725-01404
Parcel: 12702274B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0725-01404
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2025 Commercial Electrical Express APPROVED
07/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/24/2025 Outdoor Lighting Express REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0725-01404 (5402 E SPEEDWAY BL TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).


Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. The provided City of Tucson Lumen calculations table is not correct. For instance the Calculations table shows 24 Fixture ‘A’, but with zero lumens. The lighting Fixture Schedule for Fixture ‘A’ Shows a lumen count of 15,009 lumens per fixture.
2. Please update the Calculations table to include all site lighting fixtures and lumen counts. The Light Fixture Schedule shows 4 different fixtures, while the calculations table only shows 2.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/24/2025 PDSD Application Completeness Express REVIEW COMPLETED