Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0725-01399
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/07/2025 | Commercial Building | APPROVED | |||
| 08/08/2025 | Commercial Mechanical | APPROVED | |||
| 08/08/2025 | Commercial Plumbing | APPROVED | |||
| 08/06/2025 | Site Zoning | APPROVED | |||
| 07/31/2025 | Site Engineering | NOT REQUIRED | |||
| 08/08/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/23/2025 | Addressing Validation | REQUIRES RESUBMIT | It appears the site plan uploaded lists multiple addresses, each individual address requires its own permit. This permit is for the identified main address of 1104 S Craycroft Rd only, please start new permits for all other addresses/units. Please provide a site plan that lists only the main address of 1104 S Craycroft Rd. | ||
| 08/01/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0725-01399 (1104 S CRAYCROFT RD TUCSON, AZ 85711) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf 2. Provide an electrical plan showing any/all electrical work. Include an electrical floor or site plan showing the location of all new electrical work and equipment. Plumbing and Mechanical plans show new equipment being added that needs to be included in the updated electrical plans. RCP-1 & EF-1. Plans shall include, but may not be limited to items below: 3. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40. 4. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4. 5. Provide new and updated panel schedules for the 200A panel, showing the circuits that are being modified, added or removed. NEC arts;300 and 408.4. 6. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 08/02/2025 | Fire New Construction | REVIEW COMPLETED | |||
| 07/23/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |