Permit Number: TC-COM-0725-01382
Parcel: 140200220

Address:
841 E BANTAM RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0725-01382
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/25/2025 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide the structural calculations; sealed by an Arizona licensed design professional, used to design the ramada construction with the next submittal. IBC 107.2.7
2. Please provide a statement of special inspections for this specific to this pro, as well as listing the required special inspections and test required for each special inspection. IBC 107.2.1, IBC 1704, IBC 1705
3. Sheet S3.0: Please amend the plans to provide drawings and details for the roof drainage. IBC 107.2.1 The method cannot be determined and the detail callout reference 2/S1.0 appears to be a footing detail.
4. Sheet S2.0: Please review and update the Detail Keynotes for clarity. IBC 107.2.1 For example.
Keynote 13. BOND BREAKER. And it appears to be pointing to vertical rebar
Keynote 14. 4” #2500 CONCRETE SLAB OVER 4" AB COMPACTED 98%. the arrow is pointing to the masonry column.
Keynote 15. BEAM-REFER TO FRAMING PLAN (SHEET S1.1) FOR SIZE. Is indicated twice and appears to be pointing towards expansion joint material on the second listing
Keynote 17. SIMPSON 'LU210Z' JOIST HANGER @ EA. RAFTER. Appears to be pointing towards the floor slab.
5. Please provide a code analysis for the new structure, indicating Construction type, Occupancy, square footage, number of occupants, Fire sprinklers Yes,No, etc. IBC 107.2.1
08/26/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0725-01382
841 E BANTAM RD. – R-2
Religious Use - Open Ramada Addition on the rear of the building (1st Review)

TRANSMITTAL DATE: August 26, 2025

COMMENTS: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.

This site is located in the R-2 zone (UDC 4.7.9). Religious Use is a permitted use in this zone (Table 4.8-2).

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/25/2025 Fire New Construction REVIEW COMPLETED
08/12/2025 PDSD Application Completeness Express REVIEW COMPLETED