Permit Number: TC-COM-0725-01367
Parcel: 13401002D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0725-01367
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/16/2026 Commercial Plumbing REQUIRES RESUBMIT 1. Provide a detail showing the design of the sump, the discharge piping, valves, level controls, and maximum discharge level. Reference: Section 712.3, IPC 2018.
2. Provide calculations to show that the proposed grinder pump has the capacity and head needed to meet the peak flow into the sump, a full-flow velocity of 2 feet per second in the discharge pipe and develop the required lift. Reference: Section 712.4.2, IPC 2018.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
06/10/2026 PDSD Application Completeness Express REVIEW COMPLETED