Permit Number: TC-COM-0725-01314
Parcel: 141451070

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0725-01314
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2025 Commercial Plumbing Standard APPROVED
07/14/2025 Site Engineering Standard APPROVED
08/04/2025 Water - PDSD Standard APPROVED
08/04/2025 Commercial Mechanical Standard NOT REQUIRED
07/21/2025 Fire New Construction Standard NOT REQUIRED
08/04/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/01/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide structural calculations and construction drawings wit your next submittal. per The City of Tucson Commercial Submittal Checklist and IBC 107.2.1
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/24/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0725-01314 (6456 E PASEO BARANDA TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide the electrical requirements and manufacturer’s installation instructions and specification sheets for the Solar Lights.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/24/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0725-01314 (6456 E PASEO BARANDA TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).


Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. REF Sheet 3 of 22, Construction Keynotes #24. Multiple Solar Lights are being added and require compliance with the adopted outdoor lighting code.
2. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
4. Show compliance with total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2.
5. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded.

6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

7. Specify any exceptions used.

8. Provide Curfew lighting controls If applicable Per section 403.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/31/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0725-01314 - TD-DEV-0725-00178
6456 E PASEO BARANDA - PAD-7
La Estancia Park Amenities (1st Review)

TRANSMITTAL DATE: ‎July 31, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in PAD-7 (UDC 4.7.24).

1. Zoning has reviewed the building permit for compliance with development package (DP) TD-DEV-0725-00178 and although it appears that the building plan is in compliance until the DP is approved by all review agencies Zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/14/2025 PDSD Application Completeness Express REVIEW COMPLETED