Permit Number: TC-COM-0724-01469
Parcel: 124161420

Address:
885 E 22ND ST

Review Status: Requires Resubmit

Review Details: RESTAMP - COMMERCIAL v.1

Permit Number - TC-COM-0724-01469
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2024 Site Zoning APPROVED
11/14/2024 Water - PDSD APPROVED
11/22/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/14/2024 Commercial Mechanical REQUIRES RESUBMIT The mechanical comments dated 09/11/24 have not been resolved:
Verify that general room exhaust is provided for any cooking appliance that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance (e.g., 2 microwave ovens, 2 hot dog rollers, and a Turbo Chef oven). Reference: Section 507.1, exception 2 and 507.3, IMC 2018.