Permit Number: TC-COM-0724-01468
Parcel: 13708021E

Address:
5663 S 12TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0724-01468
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/19/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). Reference: Section C503.4, IECC 2018.
2. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems moving than 2,000 CFM. Reference: Section 606.2.1, IMC 2018, as amended by the City of Tucson.
3. Secure the refrigerant circuit access ports of the HVAC units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018.
08/01/2024 PDSD Application Completeness REVIEW COMPLETED