Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/19/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/19/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). Reference: Section C503.4, IECC 2018. 2. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems moving than 2,000 CFM. Reference: Section 606.2.1, IMC 2018, as amended by the City of Tucson. 3. Secure the refrigerant circuit access ports of the HVAC units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018. |
||
08/01/2024 | PDSD Application Completeness | REVIEW COMPLETED |