Permit Number: TC-COM-0724-01462
Parcel: 123052170

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01462
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2024 Water - PDSD APPROVED
08/28/2024 Site Engineering NOT REQUIRED
08/28/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT TC-COM-0824-01604 • Review new files (1)
• Studio Session 455-470-674
2308 N CAMPBELL AV TUCSON, AZ 85719
08/28/2024 External Reviewers - Stantec REQUIRES RESUBMIT August 15, 2024
1st Review

Centre LLC.
Attn: Burc Maruflu
5742 N. Camino Delmar
Tucson, Arizona 85718

Re: SAVAYA COFFEE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01462 and TC-COM-0824-01604
Stantec Project Number: 185215066
Stantec File Number: TUC-24-105

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M/F-1 V-B 3,396 278 No No
B V-B 1,809 TBD No No
Separate Permits: Solar awning.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate on the cover page that the solar awning is to be provided as part of this project and is to be submitted as a separate permit (not a deferred submittal).

3. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet A1

1. The occupant load calculations indicate the counting of seats. Please calculate the occupant load for the dining portion as 15 net. The actual occupant load can only be used with an appeal to the building official. [Ref. IBC 2018 Sec. 1004.5]

2. Please include Group F-1 occupancy classification along with the Group M indicated as the process of the bean roasting and packaging would more closely fall under the Group F-1. {Please note: This does not require occupancy separation or any additional protection requirements. It is more for certificate of occupancy clarification.}

3. Please include in the scope of work the roof repair of the adjacent tenant space to the south.

Sheet A2

1. The occupant load of 141 indicated at Note 2 of the exit requirements section conflicts the occupant load of 73 on sheet A1. Please clarify and revise.

Sheet A3

1. Please revise the door mark indicated for the back door. The door mark 5 is shown to be a 4’0” wide barn door. When scaled this door is 34”. Please revise.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
08/26/2024 Site Zoning REQUIRES RESUBMIT MASTER SET OF CONSTRUCTION PLANS ARE LOCATED WITH PERMIT: TC-COM-0724-01462 (2310 N CAMPBELL AV TUCSON, AZ 85719) TENANT IMPROVEMENT with reviews to be conducted for: TC-COM-0824-01604 (2308 N CAMPBELL AV TUCSON, AZ 85719) ROOF REPAIR ONLY


FROM: PDSD Zoning Review

PROJECT:
TC-COM-0724-01462 & TC-COM-0824-01604
2310 N CAMPBELL AV. – C-1
TI - Food Service & roof repair (1st Review)

TRANSMITTAL: August 26, 2024

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). Food Service, Excluding Soup Kitchens is a allowed use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5 and 4.9.13.O.

1. The proposed drawings show seating therefore the use is considered food service not a retail use with takeout only. Clearly demonstrate that the parking requirements are met for a food service use.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/27/2024 Fire New Construction REVIEW COMPLETED
07/30/2024 PDSD Application Completeness Express REVIEW COMPLETED