Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0724-01447
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/09/2024 External Reviewers - Stantec REQUIRES RESUBMIT September 9, 2024
2nd Review

Dean Alan Architects, PLLC.
Attn: Angela Gee
5151 East Broadway Blvd, Suite 1050
Tucson, Arizona 85711

Re: CPA OFFICES AT MO BUILDING
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01447
Stantec Project Number: 185215066
Stantec File Number: TUC-24-102

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 4,391 30 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Addressed.

Sheet T1

1. Addressed.

2. Addressed.

Sheet A0.1

1. Previous Comment: Exit access stairways that connect levels in the same story are not permitted as part of an accessible means of egress. The stair located at the back exit is an exit access stair connecting levels of the same story. Please revise. [Ref. IBC 2018 Sec. 1009.3.1] Still Required: The response to comments indicates the use of the main entrance as the only exit. The common path of travel for the rooms is measured “as the crow flies” on the Life Safety Plan. Means of egress is path of vertical and horizontal travel (right angles). When measured this way, the office/conference area common path of travel distance is 110’. This exceeds the maximum common path of travel distance of 100’. Please revise. [Ref. IBC 2018 Sec. 202]

STRUCTURAL COMMENTS

General

1. Addressed.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. Addressed.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
09/16/2024 Fire New Construction REQUIRES RESUBMIT -Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
09/03/2024 PDSD Application Completeness REVIEW COMPLETED