Permit Number - TC-COM-0724-01447
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2024 Site Zoning APPROVED
08/22/2024 Water - PDSD APPROVED
08/27/2024 Site Engineering NOT REQUIRED
08/27/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/13/2024 External Reviewers - Stantec REQUIRES RESUBMIT August 5, 2024
1st Review

Dean Alan Architects, PLLC.
Attn: Angela Gee
5151 East Broadway Blvd, Suite 1050
Tucson, Arizona 85711

Re: CPA OFFICES AT MO BUILDING
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0724-01447
Stantec Project Number: 185215066
Stantec File Number: TUC-24-102

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 4,391 30 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please revise the Floor Plan sheet as it should be labeled according to the sheet index as A1.2 but it is labeled A1.1 on the sheet.

Sheet T1

1. Please provide plumbing fixture calculations for the proposed tenant improvement. [Ref. IBC 2018 Sec. 2902.1]

2. Please provide a service sink and water fountain in accordance with Section 2902.1 of the 2018 IBC. {This comment has been included in the Plumbing Comments Section as well.}

Sheet A0.1

1. Exit access stairways that connect levels in the same story are not permitted as part of an accessible means of egress. The stair located at the back exit is an exit access stair connecting levels of the same story. Please revise. [Ref. IBC 2018 Sec. 1009.3.1]

STRUCTURAL COMMENTS

General

1. Please provide a structural analysis for the 3 proposed condensing units on the roof. [Ref. IEBC 2018 Sec. 706.2]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. Please provide a service sink and water fountain in accordance with Section 2902.1 of the 2018 IBC.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
08/22/2024 Fire New Construction REQUIRES RESUBMIT Resolve all building comments
john.vincent@tucsonaz.gov
07/26/2024 PDSD Application Completeness REVIEW COMPLETED