Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0724-01436
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2025 | Commercial Building | APPROVED | |||
| 01/08/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/08/2025 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0724-01436 (805 E 36TH ST TUCSON, AZ 85713) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Sheet E1, 1 line keynote #3, indicates that the panel is obsolete, but suitable for disconnect/feeder. Please clarify and provide documentation to show compliance with NEC 110.3. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||