Permit Number: TC-COM-0724-01425
Parcel: 137055530

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0724-01425
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2024 Site Zoning APPROVED
08/12/2024 Water - PDSD APPROVED
08/12/2024 Site Engineering NOT REQUIRED
08/12/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/31/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 7/31/2024 10:54:07 AM
1. General: The construction documents do not provide an existing floor plan. Provide a detailed existing floor plan.
2. General: The construction documents do not provide a demolition plan. Provide a detailed demolition plan.





Mechanical(M) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 7/31/2024 11:05:27 AM
1. General: Please demonstrate compliance with the 2018 International Energy Conservation Code (2018 IECC), as adopted and amended by the City of Tucson for any new mechanical equipment. ◦ The available options are to meet the prescriptive requirements of 2018 IECC Chapter 4; meet the requirements of the 2016 edition of AHRI/ASHRAE 90.1 (Energy Standard for Buildings Except Low-rise Residential Buildings) or an energy analysis of the proposed building. (2018 IECC Section C401.2) ◦ COMcheck is an accepted alternative to compliance. COMcheck is a free energy conservation compliance software through the U.S. Department of Energy (US DOE) and is available online.
2. General: No roof plan has been provided for the mechanical systems. Provide roof plans that indicate the location of all new and existing equipment along with exhaust terminations





Electrical(E) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 7/31/2024 11:16:18 AM
1. General: Please demonstrate compliance with the 2018 International Energy Conservation Code (2018 IECC), as adopted and amended by the City of Tucson for any new mechanical equipment. ◦ The available options are to meet the prescriptive requirements of 2018 IECC Chapter 4; meet the requirements of the 2016 edition of AHRI/ASHRAE 90.1 (Energy Standard for Buildings Except Low-rise Residential Buildings) or an energy analysis of the proposed building. (2018 IECC Section C401.2)
◦ COMcheck is an accepted alternative to compliance. COMcheck is a free energy conservation compliance
software through the U.S. Department of Energy (US DOE) and is available online.





Plumbing(P) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 7/31/2024 11:14:37 AM
1. Sheet P1.0: The plans indicate the installation of a grease interceptor, however, no sizing calculations have been
provided. Provide grease interceptor sizing calculations and all applicable details in accordance with 2018 IPC Section
1003.3.7.
08/08/2024 Fire New Construction REQUIRES RESUBMIT -Sheet G1.0, deferred submittals. You indicate there is an existing fire alarm and ansul hood. Verify these systems are in the building, otherwise remove from the deferred submittals.

-Explain the following note found on coversheet G1.0.
WATER-FLOW NOTIFICATION DEVICES.
AN APPROVED AUDIBLE/VISUAL NOTIFICATION
APPLIANCE SHALL BE INSTALLED IN A NORMALLY
OCCUPIED INTERIOR AREA OF EACH BUILDING OR
EACH INDIVIDUAL TENANT SPACE AT THE TIME OF
A TENANT IMPROVEMENT. ADA RESTROOMS
WITHIN THE SAME AREA SHALL HAVE A VISUAL
NOTIFICATION APPLIANCE LOCATED WITHIN THE
ROOM. SUCH SPRINKLER WATER FLOW
NOTIFICATION DEVICES SHALL BE ACTIVATED BY
THE WATER FLOW OF A SINGLE SPRINKLER
INSTALLED IN THE SYSTEM

john.vincent@tucsonaz.gov
5203495581
07/26/2024 PDSD Application Completeness REVIEW COMPLETED