Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0724-01425
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/07/2024 | Site Zoning | APPROVED | |||
08/12/2024 | Water - PDSD | APPROVED | |||
08/12/2024 | Site Engineering | NOT REQUIRED | |||
08/12/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/31/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Denied Reason: Date Completed : 7/31/2024 10:54:07 AM 1. General: The construction documents do not provide an existing floor plan. Provide a detailed existing floor plan. 2. General: The construction documents do not provide a demolition plan. Provide a detailed demolition plan. Mechanical(M) Reviewer Andrew Bevis abevis@safebuilt.com Denied Reason: Date Completed : 7/31/2024 11:05:27 AM 1. General: Please demonstrate compliance with the 2018 International Energy Conservation Code (2018 IECC), as adopted and amended by the City of Tucson for any new mechanical equipment. ◦ The available options are to meet the prescriptive requirements of 2018 IECC Chapter 4; meet the requirements of the 2016 edition of AHRI/ASHRAE 90.1 (Energy Standard for Buildings Except Low-rise Residential Buildings) or an energy analysis of the proposed building. (2018 IECC Section C401.2) ◦ COMcheck is an accepted alternative to compliance. COMcheck is a free energy conservation compliance software through the U.S. Department of Energy (US DOE) and is available online. 2. General: No roof plan has been provided for the mechanical systems. Provide roof plans that indicate the location of all new and existing equipment along with exhaust terminations Electrical(E) Reviewer Andrew Bevis abevis@safebuilt.com Denied Reason: Date Completed : 7/31/2024 11:16:18 AM 1. General: Please demonstrate compliance with the 2018 International Energy Conservation Code (2018 IECC), as adopted and amended by the City of Tucson for any new mechanical equipment. ◦ The available options are to meet the prescriptive requirements of 2018 IECC Chapter 4; meet the requirements of the 2016 edition of AHRI/ASHRAE 90.1 (Energy Standard for Buildings Except Low-rise Residential Buildings) or an energy analysis of the proposed building. (2018 IECC Section C401.2) ◦ COMcheck is an accepted alternative to compliance. COMcheck is a free energy conservation compliance software through the U.S. Department of Energy (US DOE) and is available online. Plumbing(P) Reviewer Andrew Bevis abevis@safebuilt.com Denied Reason: Date Completed : 7/31/2024 11:14:37 AM 1. Sheet P1.0: The plans indicate the installation of a grease interceptor, however, no sizing calculations have been provided. Provide grease interceptor sizing calculations and all applicable details in accordance with 2018 IPC Section 1003.3.7. |
||
08/08/2024 | Fire New Construction | REQUIRES RESUBMIT | -Sheet G1.0, deferred submittals. You indicate there is an existing fire alarm and ansul hood. Verify these systems are in the building, otherwise remove from the deferred submittals. -Explain the following note found on coversheet G1.0. WATER-FLOW NOTIFICATION DEVICES. AN APPROVED AUDIBLE/VISUAL NOTIFICATION APPLIANCE SHALL BE INSTALLED IN A NORMALLY OCCUPIED INTERIOR AREA OF EACH BUILDING OR EACH INDIVIDUAL TENANT SPACE AT THE TIME OF A TENANT IMPROVEMENT. ADA RESTROOMS WITHIN THE SAME AREA SHALL HAVE A VISUAL NOTIFICATION APPLIANCE LOCATED WITHIN THE ROOM. SUCH SPRINKLER WATER FLOW NOTIFICATION DEVICES SHALL BE ACTIVATED BY THE WATER FLOW OF A SINGLE SPRINKLER INSTALLED IN THE SYSTEM john.vincent@tucsonaz.gov 5203495581 |
||
07/26/2024 | PDSD Application Completeness | REVIEW COMPLETED |