Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-0724-01424
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/02/2024 | Commercial Building | APPROVED | |||
12/02/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
12/02/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Per 2017 NEC art 408.4. The panel schedules cannot be approved as submitted. Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. The identification shall include an approved degree of detail that allows each circuit to be distinguished from all others. No circuit shall be described in a manner that depends on transient conditions of occupancy. REF; 2018 IBC section 107.2.1, 2017 NEC. |
||
11/19/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |