Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0724-01415
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/12/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/12/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. The International Plumbing Code, 2018, is the controlling code for this structure, not the International Residential Code. Reference: Section 101.2, IPC 2018. 2. Verify the size of the existing water meter. Tucson Water shows an 1-1/2” meter serving this address. 3. The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length from the upstream entrance of the cleanout. Reference: Section 708.1.1, IPC 2018. 4. An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning only in the direction of flow. Reference: Section 708.1.8, IPC 2018. |
||
07/24/2024 | PDSD Application Completeness | REVIEW COMPLETED |