Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-0724-01410
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/16/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Please be advised that lighting area ‘E3’ ‘Option 1” is to be used when the Lighting is Mostly ‘LPS’ (Low Pressure Sodium) type and non full cut-off. It appears that the lighting proposed for this project is ‘Full Cut-off shielding ‘LEDs’. Therefore the ‘Option would be ‘Option 2’. This limits the allowed lumens to 250,000 per acre. Please revise the lumen calculation and resubmit. Also be advised, if a Special Inspection is required. The Special Inspection Certificate must be submitted all boxes filled out and the first Registrant seal stamped of the responsible party performing the Special Inspection. 2 Please submit lighting manufacturers cut sheets with highlighted columns showing the correct specifications of each luminaire. Ref; 2018 IBC section 107.2.1, 2012 City of Tucson Outdoor Lighting Code, 2017 NEC. Plan reviewer, Dan Sant Cruz. Email, Dan.santacruz@tucsonaz.gov. |
||
| 12/18/2024 | Site Engineering | REQUIRES RESUBMIT | see Electrical comments | ||
| 12/02/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |