Permit Number: TC-COM-0724-01410
Parcel: 10512024F

Address:
4040 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0724-01410
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/16/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Please be advised that lighting area ‘E3’ ‘Option 1” is to be used when the Lighting is Mostly ‘LPS’ (Low Pressure Sodium) type and non full cut-off. It appears that the lighting proposed for this project is ‘Full Cut-off shielding ‘LEDs’. Therefore the ‘Option would be ‘Option 2’. This limits the allowed lumens to 250,000 per acre. Please revise the lumen calculation and resubmit. Also be advised, if a Special Inspection is required. The Special Inspection Certificate must be submitted all boxes filled out and the first Registrant seal stamped of the responsible party performing the Special Inspection.

2 Please submit lighting manufacturers cut sheets with highlighted columns showing the correct specifications of each luminaire.

Ref; 2018 IBC section 107.2.1, 2012 City of Tucson Outdoor Lighting Code, 2017 NEC.

Plan reviewer, Dan Sant Cruz. Email, Dan.santacruz@tucsonaz.gov.
12/18/2024 Site Engineering REQUIRES RESUBMIT see Electrical comments
12/02/2024 PDSD Application Completeness Express REVIEW COMPLETED