Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0724-01410
Parcel: 10512024F

Address:
4040 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0724-01410
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
11/13/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The revised exterior lighting plan does not completely or clearly satisfy the requirements per the 2012 City of Tucson Outdoor Lighting Code.

1. Ref; Lumen calculations. Please clarify what is meant by “ALLOWED LUMENS FOR LIGHTING AREA E3 AND A”. Be advised, the lighting area is ‘E3’.

2. Please provide the Lighting Area and Option used per Table 401.1 for the lumen calculations.

3. How was the total Lumens allowed calculated to be 4,928,000.

4. For clarification of Luminaire Inventory, location and identification, also provide Site Power and Lighting plan without the Photometrics imposed on the plan. Be sure all exterior lighting is shown on the plan including existing to remain luminaires (Wall Packs) and must correlate with the luminaire schedule and lumen calculations. Section 104.2, 104.2.3.

5. Ref; Luminaire Schedule. Section 104.2.1

5a. The luminaire schedule shows 15 ‘WM’ luminaires as existing. Identify the optics as either ‘Full Cut-Off' or ‘Non - Shielded’.

5b. What is meant by “Lum. Lumens” and “Arr. Lum. Lumens”?

5c. Show the total lumens for each category at the end of the Luminaire column and grand total for all luminaires associated with this project Non-Shielded and Full Cut-Off as part of the luminaire schedule or provide a separate table.

6. See section 106.2 For what qualifies for a Special Inspection. (Greater than 100,000 Lumens per acre or 75% of the allowable lumens per Table 401.1, whichever is less).

Ref; 2018 IBC section 107.2.1, 2012 City of Tucson Outdoor Lighting Code, 2017 NEC.
11/15/2024 Site Engineering REQUIRES RESUBMIT TC-COM-0724-01410
4040 N ORACLE RD

Site engineering comments are as follows:
1. Development package, DP22-0262, must be approved by all reviewers before this building permit can be approved.
Ryan Insalaco
Email: ryan.insalaco@tucsonaz.gov
Phone: (520) 837-5351
10/30/2024 PDSD Application Completeness REVIEW COMPLETED