Permit Number: TC-COM-0724-01409
Parcel: 105102420

Address:
455 E WETMORE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01409
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2024 Water - PDSD APPROVED
08/26/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/12/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 8/12/2024 10:31:44 AM
1. Plan Sheet M2 - RTU #29 - Total CFM quantity for SAD (supply air drops) equals 3800 CFM. Plan Sheet M4 states on the RTU Schedule Non-Heat Mode 3200 CFM. Confirm Confirm CFM quantities for RTU #29 -
2. Plan Sheet M4 - Note #3 on the RTU schedule states "SMOKE DETECTORS ARE NOT REQUIRED IN UNITS SUPPLYING OVER 2000 CFM THAT ARE NOT CAPABLE OF SPREADING SMOKE BEYOND THE ENCLOSING WALLS, FLOORS AND CEILINGS FOR THE ROOM OR SPACE IN WHICH THE SMOKE IS GENERATED PER IMC
SECTION 606.2. - Plan Sheet A1.1 shows RTUs #28, #26 and #22 in the same distribution areas with air from all RTU mixing with each other. Confirm all units over 2000 CFM which Smoke Detectors were not installed. - Install Smoke Detectors as required by - 2018 IMC Section 606.2.1
3. General - Show on Mechanical plans the method of isolation for all units designated more than 2000 CFM for compliance as stated in Note #3 in RTU schedule on plan sheet M4 - Provide on details, separation walls, unit
locations in reference to area served, return and supply air drops serving area. - Specify for all units over 2000 CFM where Smoke Detector not installed. - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC – Section [A]107.2.1Information on construction documents.
4. General - Provide Ventilation Calculations/Schedule - 2018 IMC Section 403 Table 403.3.1.1
5. General - Provide COMcheck Mechanical Compliance Certificate or any other APPROVED program - 2018 IECC Section C403.3.2 HVAC equipment performance requirements




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 8/8/2024 10:25:35 PM
First Plumbing Review:
1). Roof Plan page A4: Roof area E5 is missing a primary roof scupper. Add a primary roof scupper adjacent to the already shown secondary roof scupper. -2018 IPC 1106.5, 1108
2). Plan page A4 or A4.2: Missing downspout & scupper sizing calculations. Add the downspout & scupper sizing calculations to the plan pages. -2018 IPC 106.3, 1108
3). Plan Page P1.1: Pharmacy water heater relief valve can't discharge to the Pharmacy restroom floor drain could cause serious energy. Route Relief valve discharge to a safe location. -2018 IPC 504.6
4). Plan page MP1: Irrigation Riser missing backflow device. Add backflow device in accordance with -2018 IPC 608.17.5
5). Plan Page GP1: Missing grease interceptor sizing calculations. Add grease interceptor sizing calculations to the plumbing plans in accordance with -2018 Tucson Plumbing Code Amendments.
6). Plan page GP2 equipment schedule: Missing the drain outlet temp for the double rack oven. Provide the drain outlet temp to the double rack oven info, or add cold water injection keynote "M" to the double rack oven notes section. -2018 IPC 702.5
08/26/2024 Site Engineering REQUIRES RESUBMIT see zoning comments
08/21/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0724-01409 - TD-DEV-0324-00096
455 E WETMORE RD. – C-3
Walmart Expansion (1st Review)

TRANSMITTAL: August 21, 2024
This site is located in the C-3 zone (UDC 4.7.22) General Merchandise Sales, Large Retail Establishment is a permitted use in this zone (Table 4.8-4), subject to Mayor and Council Special Exception Procedure, Section 3.4.4 and Use Specific Standard 4.9.9.D.

1. Zoning has reviewed the building plans for compliance with development package (DP), TD-DEV-0324-00096, and the following comments need to be addressed.

2. The building gross floor area, 164,587 does not match what is shown on the DP, 163,789. Either the building plan or the DP will need to be revised so that the floor area match.

3. Until the DP is approved by all review agencies Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/22/2024 Fire New Construction REVIEW COMPLETED
07/24/2024 PDSD Application Completeness REVIEW COMPLETED