Permit Number: TC-COM-0724-01409
Parcel: 10510242A

Address:
455 E WETMORE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0724-01409
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/07/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 7/5/2025 12:54:31 PM
1. 1. E1 LIGHTING PLAN: Could not locate Keynote 16.021. Addressed
2. 2. E1.3 LIGHTING DETAILS AND SITE LIGHTING: Need to provide an interior Lighting comcheck for all areas
that have new lighting to show IECC compliance for the areas of renovation. Need to provide an exterior lighting
power Density calculation per Tucson City requirements. Both the interior lighting comcheck and the exterior lighting
calculation need to be provided for an electrical permit.
◦ Interior Comcheck submitted and Accepted
◦ Exterior Tucson City required lumens per Acre calculation NOT PROVIDED on sheet A240612D or elsewhere
in plans. Suggest to include calculation on E1.4 or sheet A240612D. Need to call out specifically which Civil
sheet if the calculation is located elsewhere in submittal. The addition of extra lighting may have made the 2017
lighting design non-compliant. Calculations are needed to assure the exterior lighting complies with Tucson
City's unique dark sky compliance requirements.
3. 3. T1 TELECOM PLAN: Missing 17.004 Keynote description. Addressed
07/03/2025 PDSD Application Completeness Express REVIEW COMPLETED