Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0724-01409
Parcel: 10510242A

Address:
455 E WETMORE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01409
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 5/8/2025 8:32:18 AM

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/5/2025 2:55:44 PM
05/08/2025 Commercial Mechanical Standard APPROVED Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 5/7/2025 3:54:48 PM
05/08/2025 Commercial Plumbing Standard APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 5/4/2025 11:47:12 PM
REVISED PLUMBING REVIEW OK
05/29/2025 Site Engineering Standard APPROVED
05/27/2025 Site Zoning Standard APPROVED
05/22/2025 Water - PDSD Standard APPROVED
05/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/08/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 5/7/2025 5:28:55 PM
1. 1. E1 LIGHTING PLAN: Could not locate Keynote 16.021.
2. 2. E1.3 LIGHTING DETAILS AND SITE LIGHTING: Need to provide an interior Lighting comcheck for all areas
that have new lighting to show IECC compliance for the areas of renovation. Need to provide an exterior lighting
power Density calculation per Tucson City requirements. Both the interior lighting comcheck and the exterior lighting
calculation need to be provided for an electrical permit.
3. 3. T1 TELECOM PLAN: Missing 17.004 Keynote description.
05/19/2025 Fire New Construction Standard REVIEW COMPLETED The following items need separate submittal and permits:
1. Fire Alarm Upgrades
2. Fire Sprinklers System Upgrades
3. CO2 systems, Operational Permit
4. Propane: Operational permit
5. Kitchen hood systems fire suppression.