Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0724-01409
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/23/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/06/2025 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 1/3/2025 10:46:22 AM 1. (UNRESOLVED) - Plan Sheet M2 - RTU #29 - Total CFM quantity for SAD (supply air drops) equals 3800 CFM. Plan Sheet M4 states on the RTU Schedule Non-Heat Mode 3200 CFM. Confirm Confirm CFM quantities for RTU #29 - 2. (UNRESOLVED) - Plan Sheet M4 - Note #3 on the RTU schedule states "SMOKE DETECTORS ARE NOT REQUIRED IN UNITS SUPPLYING OVER 2000 CFM THAT ARE NOT CAPABLE OF SPREADING SMOKE BEYOND THE ENCLOSING WALLS, FLOORS AND CEILINGS FOR THE ROOM OR SPACE IN WHICH THE SMOKE IS GENERATED PER IMC SECTION 606.2. - Plan Sheet A1.1 shows RTUs #28, #26 and #22 in the same distribution areas with air from all RTU mixing with each other. Confirm all units over 2000 CFM which Smoke Detectors were not installed. - Install Smoke Detectors as required by - 2018 IMC Section 606.2.1 3. (UNRESOLVED) - General - Show on Mechanical plans the method of isolation for all units designated more than 2000 CFM for compliance as stated in Note #3 in RTU schedule on plan sheet M4 - Provide on details, separation walls, unit locations in reference to area served, return and supply air drops serving area. - Specify for all units over 2000 CFM where Smoke Detector not installed. - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC – Section [A]107.2.1Information on construction documents. 4. (RESOLVED) - General - Provide Ventilation Calculations/Schedule - 2018 IMC Section 403 Table 403.3.1.1 5. (UNRESOLVED) - General - Provide COMcheck Mechanical Compliance Certificate or any other APPROVED program - 2018 IECC Section C403.3.2 HVAC equipment performance requirements. Provide Response Narrative Letter: RESUBMITTAL DIRECTIONS: • All corrections must be clouded, delta numbered, with a brief explanation within the plan sheet or the title block of the sheet. For corrections or revision to whole plan sheets, you need only cloud the sheet number and provide the delta identification number, with a brief explanation of the change(s). • As part of the resubmittal, please collate all revised sheets into the electronic document (PDF) and submit a complete and full plan set. We cannot accept individual sheets in response to review comments, since the entire plan set is required for approval and permitting. • Please include with the resubmittal a separate response narrative, which is numbered or itemized to correspond to each of the noted plan review comments items. • This response narrative must clearly address how each issue was corrected or resolved and indicate where the information may be found within the construction documents. The response narrative must be typewritten, on a letterhead noting the project name, with the Permit Application Number. Failure to provide this response narrative may result in review delays or rejection of the resubmittal. • Once all electronic construction documents (plan sheets, energy compliance certificates, reports, calculations, etc.) have been revised according to the above directions. Please resubmit the complete revised plan set with a separate copy of response narrative PDF through the municipality to complete the review. • Review of revised construction documents in response to this letter may take upwards of 5 (five) business days, depending on the size of the project and the volume of plans in queue at time of resubmittal. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 1/5/2025 8:40:33 PM Second Plumbing Review: Comments 3 & 4 Remain Resolved-1). Roof Plan page A4: Roof area E5 is missing a primary roof scupper. Add a primary roof scupper adjacent to the already shown secondary roof scupper. -2018 IPC 1106.5, 1108 Resolved-2). Plan page A4 or A4.2: Missing downspout & scupper sizing calculations. Add the downspout & scupper sizing calculations to the plan pages. -2018 IPC 106.3, 1108 Unresolved-3). Plan Page P1.1: Pharmacy water heater relief valve can't discharge to the Pharmacy restroom floor drain could cause serious energy. Route Relief valve discharge to a safe location. -2018 IPC 504.6 Unresolved-4). Plan page MP1: Irrigation Riser missing backflow device. Add backflow device in accordance with -2018 IPC 608.17.5 Resolved-5). Plan Page GP1: Missing grease interceptor sizing calculations. Add grease interceptor sizing calculations to the plumbing plans in accordance with -2018 Tucson Plumbing Code Amendments. Resolved-6). Plan page GP2 equipment schedule: Missing the drain outlet temp for the double rack oven. Provide the drain outlet temp to the double rack oven info, or add cold water injection keynote "M" to the double rack oven notes section. -2018 IPC 702.5 |
||
| 01/23/2025 | Site Engineering | REQUIRES RESUBMIT | see zoning comments | ||
| 01/21/2025 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-COM-0724-01409 - TD-DEV-0324-00096 455 E WETMORE RD. – C-3 Walmart Expansion (2nd Review) TRANSMITTAL: January 21, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-3 zone (UDC 4.7.22) General Merchandise Sales, Large Retail Establishment is a permitted use in this zone (Table 4.8-4), subject to Mayor and Council Special Exception Procedure, Section 3.4.4 and Use Specific Standard 4.9.9.D. 1. Zoning has reviewed the building plans for compliance with development package (DP), TD-DEV-0324-00096, and the following comments need to be addressed. 2. This comment was not addressed. The building gross floor area, 164,587 does not match what is shown on the DP, 163,789. Either the building plan or the DP will need to be revised so that the floor area match. 3. Until the DP is approved by all review agencies Zoning cannot approve the building plans. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |