Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-0724-01402
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2024 | Commercial Electrical | APPROVED | |||
| 08/26/2024 | Commercial Plumbing | APPROVED | |||
| 08/26/2024 | Site Zoning | APPROVED | |||
| 08/27/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/26/2024 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please provide structural calculations used in the design of the new Roof Top Unit with the next submittal. IBC 107.2.7 Additionally, please include any required special inspections associated with this portion of the project. Sheet A0.0: Please amend list of applicable codes to include the 2018 International Existing Building Code (IEBC) to the list of current governing codes. IBC 107.2.1 Sheet A0.0: Please amend the Occupancy type to reflect B-Ambulatory Care Facility and additionally, demonstrate on plans compliance with IBC Section 422. For example. A. 422.2 Separation - Fire partitions, etc. B. 422.3 Smoke compartments - C. 422.3.1 Means of egress. Defend in Place requirements D. 422.3.2 Refuge area for each nonambulatory care recipient E. 422.3.3 Independent egress from each smoke compartment F. 422.5 Fire alarm systems with automatic smoke detection G. 422.6 Electrical systems. Amend plans to indicate the essential electrical system for electrical components, equipment and systems shall be designed and constructed in accordance with the provisions of Chapter 27 and NFPA 99. IBC 107.2.1 Sheet A0.0: Please add a note on plan to clarify if fire sprinkler/alarm modifications are necessary as a part of the proposed scope of work. If so, further indicate with a note on plan that fire sprinklers/alarm will be a separate submittal IBC 107.3.4.1 Sheet A1.1: Please amend the plans to provide wall type legend and indicate type of each wall on the floor plan, or otherwise indicate the wall types for clarity to include New and Existing. IBC 107.2.1 For example, I assume all wall in the new tenant area are new; however I’m not sure, and only one instance of Floor plan Keynote #9 is show on the plan and Keynote #13 is not found on the plan. Sheet A1.2: Please amend the Exiting plan to show the number of occupants for every room and space. IBC 107.2.3 Additionally, update the code analysis, if necessary, to reflect the new occupant load. Sheet A1.2: Please amend the Exiting plan to show the occupant load factor and area for every room and space. IBC 1004.5 Sheet A1.2: Please amend the Exiting plan to include the furniture plan. IBC 107.2.1 Please review the Hazardous Material Quantities Table and provide a list for this facility if required. Please note that additional information such as chemical storage, fire separation from storage area may be required. IBC Section 307 Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 08/26/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Verify the air balance for the DOAS unit shown in detail 8/M2.1, the outside air flowrate does not agree with the schedule for the unit. Reference: Section 304.1, IMC 2018. | ||
| 08/26/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 08/13/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |