Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0724-01394
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/05/2024 | Commercial Electrical | APPROVED | |||
08/08/2024 | Commercial Mechanical | APPROVED | |||
08/01/2024 | Site Zoning | APPROVED | |||
08/08/2024 | Water - PDSD | APPROVED | |||
08/06/2024 | Site Engineering | NOT REQUIRED | |||
08/09/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/09/2024 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. 1. Sheet TS1: Please amend plans to provide a sheet index that includes all the drawing sheets, each with unique labels, in this permit’s scope. IBC 107.2.1For example, sheets labeled P1.1, P3.0& P4.0 are listed in the index and are not included in the plan set. Additionally (2) sheets are included with P2 sheet label 2. Sheet TS1: Please amend the list of deferred submittals to add a note to not install until approved. IBC 107.3.4.1 3. Sheet TS1: Please verify the construction type used is Type IV. IBC 602.4 Additionally, if IV is the construction type, update the Fire-Resistance Ratings for the Buildings Elements as indicated in IBC Table 601. For example, all Interior walls and partitions shall be of solid wood construction formed by not less than two layers of 1-inch matched boards or laminated construction 4 inches thick, or of 1-hour fire-resistance-rated construction. 4. Sheet A1.1: Please amend drawing to show the path of egress from doors 101A and 101B to the exit include is a demarcated, minimum 44-inch-wide aisle and by a full- or partial-height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions. IBC 1016.2 #5 exception 2.4 5. Sheet A2.1: Please elaborate on the meaning of Electric Strike in the Notes Column of the Door Schedule. For example, are these electronically controlled access doors? If so, please describe how the hardware is operates. IBC 107.2.1 Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
08/08/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Show the size, route, and termination of the drain for the water heater pan. Reference: Section 504.7, IPC 2018. | ||
08/02/2024 | Fire New Construction | REQUIRES RESUBMIT | -IFC 1016.2 #5, Exception #2.4. The second exit from the M shall have a minimum 44" wide isle defined by full or partial height fixed walls per the exception. john.vincent@tucsonaz.gov 5203495581 |
||
07/22/2024 | PDSD Application Completeness | REVIEW COMPLETED |