Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0724-01392
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/08/2024 | Commercial Structural | NOT REQUIRED | |||
08/08/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/23/2024 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0724-01392 (702 W SILVERLAKE RD TUCSON, AZ 85713) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide an updated siteplan showing the location of the panel to be replaced, NEC 110.2, 2018 IBC 107.1. 2. Clarify if this is a like-for-like replacement or amp-rating upgrade. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
07/22/2024 | PDSD Application Completeness | REVIEW COMPLETED |