Permit Number: TC-COM-0724-01387
Parcel: 117067310

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0724-01387
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/19/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please amend plans to provide a complete floor plan for the unit and outdoor seating area and provide a means of egress plan. IBC 107.2.3
2. Please amend exit analysis to indicate a minimum of two exits from building as required when an “A“ occupancy exceeds 49 occupants. IBC 1006.2.1
3. Please amend plans to show required 10 inch kick plate at bottom of gate. 404.2.9 2009 ICC A117.1
A. Gates serving the means of egress system shall comply with the requirements of this section. Gates used as a component in a means of egress shall conform to the applicable requirements for doors. 1010.2 Gates.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
08/19/2024 Fire New Construction REQUIRES RESUBMIT -Provide an exiting plan. Include all the suites with the entire occupant load. It appears all occupants are exiting through one patio exit gate. OL greater than 49 requires two exits that are appropriately spaced. IFC 1006
john.vincent@tucsonaz.gov
5203495581
08/19/2024 Site Engineering REQUIRES RESUBMIT 1. See zoning comments
08/15/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0724-01387
350 E CONGRESS ST Unit: 150 - OCR-2
Patio Expansion (1st review)

TRANSMITTAL DATE:‎ August 15, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the OCR-2 zone (UDC 4.7.27). Mixed Use is a permitted use in this zone (Table 4.8-4).

1. COMMENT: Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The Administrative Manual can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes-and-Plans/Zoning-Code#section-1.

2. COMMENT: Rio Nuevo Area (RNA) and Historic review will be required.

If you have any questions about this transmittal, contact Nicholas Martell at (520) 837-6933 or email Nicholas.Martell@tucsonaz.gov.
07/18/2024 PDSD Application Completeness REVIEW COMPLETED