Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0724-01387
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/19/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/19/2024 | Commercial Structural | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. 1. Please amend plans to provide a complete floor plan for the unit and outdoor seating area and provide a means of egress plan. IBC 107.2.3 2. Please amend exit analysis to indicate a minimum of two exits from building as required when an “A“ occupancy exceeds 49 occupants. IBC 1006.2.1 3. Please amend plans to show required 10 inch kick plate at bottom of gate. 404.2.9 2009 ICC A117.1 A. Gates serving the means of egress system shall comply with the requirements of this section. Gates used as a component in a means of egress shall conform to the applicable requirements for doors. 1010.2 Gates. Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
08/19/2024 | Fire New Construction | REQUIRES RESUBMIT | -Provide an exiting plan. Include all the suites with the entire occupant load. It appears all occupants are exiting through one patio exit gate. OL greater than 49 requires two exits that are appropriately spaced. IFC 1006 john.vincent@tucsonaz.gov 5203495581 |
||
08/19/2024 | Site Engineering | REQUIRES RESUBMIT | 1. See zoning comments | ||
08/15/2024 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-0724-01387 350 E CONGRESS ST Unit: 150 - OCR-2 Patio Expansion (1st review) TRANSMITTAL DATE: August 15, 2024 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the OCR-2 zone (UDC 4.7.27). Mixed Use is a permitted use in this zone (Table 4.8-4). 1. COMMENT: Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The Administrative Manual can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes-and-Plans/Zoning-Code#section-1. 2. COMMENT: Rio Nuevo Area (RNA) and Historic review will be required. If you have any questions about this transmittal, contact Nicholas Martell at (520) 837-6933 or email Nicholas.Martell@tucsonaz.gov. |
||
07/18/2024 | PDSD Application Completeness | REVIEW COMPLETED |