09/16/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/16/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Replacement of an AC unit will require a heating/cooling load calculation to justify the capacity of the unit being installed (Sections R403.7, IECC 2018). The unit will also have to comply with Sections R403.1 and R503.1.2, IECC 2018 for efficiency. Provide the manufacturer’s name, the model number and the manufacturer’s efficiency data for the proposed unit. | ||