Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0724-01377
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/18/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/03/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0724-01377 (4202 E 22ND ST TUCSON, AZ 85711) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). >>> The design must be prepared and sealed by a Registered Design Professional. 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional, i.e. an Electrical Engineer. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 04/18/2025 | Commercial Structural | REQUIRES RESUBMIT | **NEW COMMENT FROM SECOND REVIEW**This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete structural plans, design, and calculations, sealed by an Arizona Registrant(STRUCTURAL ENGINEER). Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section IBC107.2.7 1. **REWORDED and EXPANDED** Please have licensed design professional an Arizona licensed Registrant (STRUCTURAL ENGINEER) provide an evaluation of the existing roof and prepare analysis showing the existing roof can resist the new load of the rooftop PV system. IBC 107.2.7 ** The Arizona licensed Registrant (STRUCTURAL ENGINEER) will provide an evaluation of the existing roof structural system and determine if it is adequate to support the new loads of the Rooftop PV System 2. **REWORDED and EXPANDED**2. Provide structural design and calculations prepared, sealed, signed, and dated by an Arizona licensed Registrant (STRUCTURAL ENGINEER) for the addition of the new rooftop PV system indicating the method of attachment of the Rooftop PV system and uplift resistance. IBC 107.2.7 Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 04/18/2025 | Site Engineering | REQUIRES RESUBMIT | TC-COM-0724-01377 4202 E 22ND ST See previous engineering comments. This project is within a regulated floodplain and requires a Floodplain Use Permit (FUP) Chris Arrington chris.arrington@tucsonaz.gov |
||
| 04/03/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |